{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3220-1YH62-1CB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3220-1YH62-1CB0","canonicalUrl":"https://aoctrl.com/siemens/6SL3220-1YH62-1CB0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3220-1YH62-1CB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YH62-1CB0, 450 kW, 500-690 V 3-phase, IP20, size FSH, with integrated RFI C3 filter and MODBUS RTU/BACnet MS/TP/USS.","salesMarkdown":"## 450 kW overload profile — built for pump and fan duty The 6SL3220-1YH62-1CB0: Rated power 450 kW with a 135% overload capability for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — this duty cycle matches the starting and transient demands of centrifugal pumps, fans, and compressors in HVAC or water/wastewater service. The drive accepts a 3-phase supply of 500–690 V AC +10%/-20% at 47–63 Hz, covering the common industrial voltage bands in Europe, Asia, and North America without a step-down transformer. ## Integrated fieldbus and RFI filter — no option cards needed Built-in MODBUS RTU, BACnet MS/TP, and USS protocols mean the drive communicates directly with building management systems (BMS) or plant SCADA without a separate communication module — saves a slot and reduces wiring. The integrated RFI suppression filter meets category C3 for 3AC 500–690 V supplies, so the drive is suited for industrial environments where conducted emissions limits apply; no external filter needed for most installations. ## Size FSH frame — cabinet planning and ambient limits Physical dimensions are 800 x 1870 x 600 mm (L x W x H) — this is a floor-standing cabinet-mount drive; plan for a dedicated enclosure or a large panel bay with adequate ventilation clearance around the heatsink. Rated ambient temperature 0 to +45 °C with IP20 / UL open type protection — requires installation inside a cabinet that keeps dust and moisture out; no washdown or outdoor rating. ## Active production — compliance and sourcing RoHS compliant since 11-03-20; REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w — factor this into end-of-life waste reporting for the installation site. Export classification AL: N / ECCN: EAR99H — no special export license required for most destinations, simplifying cross-border procurement for global projects.","metaTitle":"Siemens 6SL3220-1YH62-1CB0 SINAMICS G120X VFD, 450 kW","metaDescription":"Siemens 6SL3220-1YH62-1CB0 SINAMICS G120X VFD, 450 kW at 135% overload for 3 s. Built-in RFI C3 filter, MODBUS RTU/BACnet MS/TP/USS.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"title":"6SL3220-1YH62-1CB0","Group Code":"R220","description":"SINAMICS G120X Rated power: 450 kW at 135% 3 s or 110% 60 s, 100% 240 s; RFI suppression filter for category C3 3AC500-690V+10/-20% 47-63Hz Ambient temperature 0 to +45 °C Size: FSH Degree of protection IP20 / UL open type Without operator panel With IO expansion Fieldbus integrated: MODBUS RTU, BACnet MS/TP,USS","Product Group":"4R53","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99H","Packaging dimensions (L x W x H)":"800.00 x 1,870.00 x 600.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 11-03-20","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://mall.industry.siemens.com/mall/Document/GetDocumentBasedOnCode?code=aHR0cHM6Ly9tYWxsLmluZHVzdHJ5LnNpZW1lbnMuY29tL3NwaWNlL2RvY3VzZXJ2aWNlL2RvY3VzZXJ2aWNlP2NvbmZpZ2lkPTE0JmRvY3UubWxmYj02U0wzMjIwLTFZSDYyLTFDQjAmZG9jdS5pbml0dHlwZT1NTEZCJmRvY3UuZ2VuZXJhdGlvbnR5cGU9VklFVyZkb2N1LnZpZXdpZD1QREYmcmVnaW9uPUFFJmxhbmd1YWdlPWVuJmRvY3UubGFuZ3VhZ2UubG9jYWxlMT1lbiZkb2N1Lmxhbmd1YWdlLmxvY2FsZTI9ZW4=', 'path_name': '64b158a5174793d3896de145ceec4028.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/sieportal_siemens/64b158a5174793d3896de145ceec4028.pdf', 'status': 1}","sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/6SL3220-1YH62-1CB0?tree=CatalogTree"},"ai":{"faq":[{"question":"What fieldbus protocols does 6SL3220-1YH62-1CB0 support?","answer":"MODBUS RTU, BACnet MS/TP, and USS are integrated — no option card needed for BMS or SCADA connectivity."},{"question":"What is the overload rating of 6SL3220-1YH62-1CB0?","answer":"135% for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — suitable for pump and fan starting transients."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3220-1YH62-1CB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3220-1YH62-1CB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}