{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3220-1YH64-0CP0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3220-1YH64-0CP0","canonicalUrl":"https://aoctrl.com/siemens/6SL3220-1YH64-0CP0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3220-1YH64-0CP0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YH64-0CP0, 500 kW, 500-690 V, 47-63 Hz, IP20, PROFIBUS DP, size FSJ.","salesMarkdown":"## 500 kW at 500-690 V — overload profile for pump and fan duty The 6SL3220-1YH64-0CP0 is a SINAMICS G120X infrastructure converter rated 500 kW at 500-690 V, 47-63 Hz, with a 135% overload for 3 seconds or 110% for 60 seconds, and 100% for 240 seconds. This overload profile matches the starting and transient demands of centrifugal pumps, fans, and compressors in HVAC and water/wastewater service — the drive handles the inrush without oversizing the power stage. The RFI suppression filter for category C3 is integrated, so the drive meets conducted emission limits for industrial second-environment installations without an external filter. Input voltage tolerance of +10/-20% covers the sag on weak utility feeds common in retrofit projects. ## Size FSJ enclosure and IP20 integration The FSJ frame size delivers 500 kW in an IP20 / UL open-type enclosure — the drive mounts in a clean indoor switchgear lineup or MCC bucket. Packaging dimensions of 1,200 x 1,857 x 800 mm indicate a substantial footprint; plan for floor-mounting with top cable entry and adequate clearance for the integrated filter and bus reactor cooling. Integrated PROFIBUS DP fieldbus eliminates a separate communication module for plants running a PROFIBUS backbone. No operator panel or IO expansion is included — the drive is commissioned via the fieldbus or a connected PC with STARTER/SINAMICS Startdrive. ## Active production and compliance documentation RoHS compliant since March 2020. REACH Article 33 disclosure notes lead (CAS 7439-92-1) above 0.1% w/w in certain components — this is a standard declaration for drives with lead-bearing solder joints and does not restrict installation under current EU exemptions.","metaTitle":"Siemens 6SL3220-1YH64-0CP0 SINAMICS G120X VFD, 500 kW","metaDescription":"Siemens 6SL3220-1YH64-0CP0 SINAMICS G120X infrastructure converter, 500 kW at 500-690 V, IP20, PROFIBUS DP, active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"Group Code":"R220","Product Group":"4R53","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99H","Packaging dimensions (L x W x H)":"1,200.00 x 1,857.00 x 800.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 11-03-20","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/6SL3220-1YH64-0CP0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/6SL3220-1YH64-0CP0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 6SL3220-1YH64-0CP0?","answer":"RoHS compliance is confirmed since March 2020. REACH Article 33 disclosure identifies lead (CAS 7439-92-1) above 0.1% w/w. Export control is AL N / ECCN EAR99H, meaning no special licensing is required for most destinations."},{"question":"What is the overload capability of this drive?","answer":"The drive delivers 135% rated current for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds. This is a variable-torque overload profile suited for pump and fan starting — not intended for constant-torque loads like conveyors or extruders without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3220-1YH64-0CP0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3220-1YH64-0CP0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}