{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3220-1YH64-1CP0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3220-1YH64-1CP0","canonicalUrl":"https://aoctrl.com/siemens/6SL3220-1YH64-1CP0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3220-1YH64-1CP0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YH64-1CP0, 500 kW, 3AC 500-690 V, IP20, PROFIBUS DP, size FSJ.","salesMarkdown":"## 500 kW at 135% overload — HVAC and water duty cycle The 6SL3220-1YH64-1CP0 is a SINAMICS G120X infrastructure converter rated for 500 kW with a 135% overload for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — this overload profile matches the typical pump and fan starting torque and short-duration demand in HVAC, water, and wastewater applications. It operates on a 3-phase supply of 500 to 690 V AC (+10%/-20%) at 47 to 63 Hz, with an ambient temperature range of 0 to +45 °C. The IP20 / UL open type enclosure is suited for installation inside a clean, dry electrical panel or equipment room. ## PROFIBUS DP and I/O expansion Fieldbus integration is via PROFIBUS DP, with an IO expansion slot available for additional I/O modules. There is no operator panel on this variant — parameterization and control are handled through the fieldbus or a connected commissioning tool. The drive includes a built-in RFI suppression filter for category C3, which covers most industrial environments in the EU. For installations requiring lower conducted emissions, an external filter may be needed.","metaTitle":"Siemens 6SL3220-1YH64-1CP0 SINAMICS G120X VFD, 500 kW","metaDescription":"Siemens 6SL3220-1YH64-1CP0 SINAMICS G120X VFD, 500 kW at 135% overload, 3AC 500-690 V, IP20, PROFIBUS DP. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"Group Code":"R220","Product Group":"4R53","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99H","Packaging dimensions (L x W x H)":"1,200.00 x 1,857.00 x 800.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 11-03-20","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/6SL3220-1YH64-1CP0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/6SL3220-1YH64-1CP0/alternatives.json"},"ai":{"faq":[{"question":"What is the group code and product group for 6SL3220-1YH64-1CP0?","answer":"The group code is R220 and the product group is 4R53. These are Siemens internal classification codes used for ordering and catalog structure."},{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance is confirmed since March 2020. The REACH Article 33 duty to inform is applicable due to lead content above 0.1% by weight. Export control classification is AL: N / ECCN: EAR99H."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3220-1YH64-1CP0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3220-1YH64-1CP0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}