{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3220-3YH68-0CB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3220-3YH68-0CB0","canonicalUrl":"https://aoctrl.com/siemens/6SL3220-3YH68-0CB0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3220-3YH68-0CB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120X infrastructure converter, 630 kW, 3AC 500-690V, IP20, Size FSJ, with Intelligent Operator Panel, integrated MODBUS RTU, BACnet MS/TP, USS.","salesMarkdown":"## 630 kW infrastructure drive — what the overload profile means for pump/fan duty The 6SL3220-3YH68-0CB0 is a SINAMICS G120X converter rated 630 kW with a 135% overload for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — this overload profile maps to pump and fan starting torque demands where the peak comes at breakaway and drops off once the impeller spins up. Input range is 3AC 500-690 V +10/-20% at 47-63 Hz, with an integrated RFI suppression filter for Category C3 environments — the filter is built in, not a bolt-on kit, which saves a panel slot and avoids the wiring between drive and filter. ## Fieldbus integration and panel fit The drive ships with MODBUS RTU, BACnet MS/TP, and USS on the base board — no fieldbus option module needed for building automation or water/wastewater networks; the BACnet MS/TP interface connects directly to the BMS controller without a gateway. Size FSJ frame with IP20 / UL open type protection — the enclosure is ventilated for convection cooling and mounts in a clean indoor panel; the 1,200 x 1,857 x 800 mm shipping package gives the rough footprint for panel layout planning. Ambient rating is 0 to +45 °C — above that the drive must be derated or cabinet-cooled; the Intelligent Operator Panel (IOP) is included for commissioning and diagnostics without a laptop. ## Lifecycle and compliance — active, RoHS, REACH Product status is active — this is a current-production drive from Siemens, not a phase-out or NRND line; available to order against BOM quantities through authorized distribution. RoHS compliant since March 2020, with a REACH Article 33 declaration for lead (CAS 7439-92-1) above 0.1% w/w in certain components — the REACH notice is a supply-chain disclosure, not a restriction on use in industrial equipment. Export control classification is AL: N / ECCN: EAR99H — no special license required for most industrial destinations, but confirm the end-use country with your compliance team.","metaTitle":"Siemens 6SL3220-3YH68-0CB0 SINAMICS G120X, 630 kW, FSJ","metaDescription":"Siemens SINAMICS G120X infrastructure converter, 630 kW at 135% overload, 3AC 500-690V, IP20, MODBUS/BACnet. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"Group Code":"R220","Product Group":"4R53","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"SINAMICS G120X infrastructure converters for HVAC/Water/Wastewater","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : EAR99H","Packaging dimensions (L x W x H)":"1,200.00 x 1,857.00 x 800.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 11-03-20","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://sieportal.siemens.com/en-ae/products-services/detail/6SL3220-3YH68-0CB0?tree=CatalogTree","alternativesUrl":"https://aoctrl.com/api/mcp/products/6SL3220-3YH68-0CB0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive carry?","answer":"RoHS compliant since March 2020, with a REACH Article 33 declaration for lead content above 0.1% w/w. Export control is AL: N / ECCN: EAR99H."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3220-3YH68-0CB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3220-3YH68-0CB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}