{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3225-0BE32-2UA0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3225-0BE32-2UA0","canonicalUrl":"https://aoctrl.com/siemens/6SL3225-0BE32-2UA0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3225-0BE32-2UA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120 Power Module PM250, 6SL3225-0BE32-2UA0, 22 kW high overload / 30 kW light overload, 380-480 VAC, IP20, without filter, regenerative capability, FSD size.","salesMarkdown":"## Power module with built-in regenerative braking The 6SL3225-0BE32-2UA0 is a SINAMICS G120 Power Module PM250 rated for 22 kW high overload (HO) and 30 kW light overload (LO) on a 380-480 VAC three-phase supply. High overload delivers 200% current for 3 seconds, 150% for 57 seconds, and 100% for 240 seconds — sized for conveyors, pumps, and fans that need short torque bursts without oversizing the drive. Light overload at 150% for 3 seconds, 110% for 57 seconds, and 100% for 240 seconds suits constant-torque applications running below rated speed. Unlike the standard PM240, this PM250 variant includes regenerative capability — it can feed braking energy back into the line rather than dumping it across a resistor. That cuts energy costs and panel heat in applications with frequent deceleration cycles, like centrifuges, hoists, or unwinders. The unit ships in a 510 x 400 x 310 mm package. RoHS compliance dates from May 2016; note the REACH Article 33 disclosure for lead (CAS 7439-92-1) above 0.1% w/w in certain components. ## Integration notes for the PM250 FSD frame This is a PM250 frame size FSD, 419 x 275 x 204 mm (HxWxD), IP20 enclosure. It requires an external Control Unit (CU) and BOP to operate — neither is included. The power module mates directly with the CU via the standard SINAMICS G120 backplane interface; no additional wiring is needed for the control link. The regenerative function is active by default on the PM250 — no external braking resistor or chopper module is required. For applications that cannot feed back to the line (e.g., generator-fed island grids), the regen can be disabled via parameter setting. Input is 380-480 VAC +10/-10%, 47-63 Hz; the unit includes no internal line filter, so external EMC filtering may be needed depending on the installation environment.","metaTitle":"Siemens 6SL3225-0BE32-2UA0 SINAMICS G120 PM250, 22/30 kW","metaDescription":"Siemens 6SL3225-0BE32-2UA0 SINAMICS G120 Power Module PM250, 22 kW high overload / 30 kW light overload, 380-480 VAC, IP20, regenerative.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"title":"6SL3225-0BE32-2UA0","Group Code":"R220","description":"SINAMICS G120 POWER MODULE PM250 WITHOUT FILTER POSSIBILITY OF REGENERATION 3AC380-480V +10/-10% 47-63HZ OUTPUT HIGH OVERLOAD: 22KW FOR 200% 3S,150% 57S,100% 240S AMBIENT TEMP 0 TO +50 DEG C OUTPUT LIGHT OVERLOAD: 30KW FOR 150% 3S,110% 57S,100% 240S AMBIENT TEMP 0 TO +40 DEG C 419 X 275 X 204 (HXWXD), FSD PROTECTION IP20 WITHOUT CONTROL UNIT AND BOP","Product Group":"9784","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"Power Modules","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : 9N9999","Packaging dimensions (L x W x H)":"510.00 x 400.00 x 310.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 11-05-16","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,772.41","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=185138&mlfb=6SL3225-0BE32-2UA0"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 6SL3225-0BE32-2UA0?","answer":"The module is RoHS compliant since May 2016 and carries a REACH Article 33 disclosure for lead (CAS 7439-92-1) above 0.1% w/w. Export control classification is AL: N / ECCN: 9N9999."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3225-0BE32-2UA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3225-0BE32-2UA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}