{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3225-0BE33-7UA0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3225-0BE33-7UA0","canonicalUrl":"https://aoctrl.com/siemens/6SL3225-0BE33-7UA0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3225-0BE33-7UA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS G120 Power Module PM250, 6SL3225-0BE33-7UA0, 37 kW high overload, 45 kW light overload, 380-480 VAC, IP20, without filter or control unit.","salesMarkdown":"## What the overload ratings mean for your motor The 6SL3225-0BE33-7UA0: The PM250 delivers 37 kW under high overload (200% for 3 s, 150% for 57 s, 100% for 240 s) at 0 to +50 °C ambient — this is the rating for constant-torque loads like conveyors or extruders that need short bursts of high torque. For variable-torque applications (pumps, fans), the light overload rating is 45 kW (150% for 3 s, 110% for 57 s, 100% for 240 s) but the ambient ceiling drops to +40 °C — plan the panel ventilation around this derating step. ## Physical fit and panel integration The module measures 499 x 275 x 204 mm (H x W x D) with IP20 finger-safe protection — it mounts inside a cabinet and needs clearance above and below for airflow; the shipping box is 600 x 400 x 310 mm. It ships without a Control Unit or BOP — you order those separately (CU240E-2, CU250S-2, etc.) and plug them into the front slot. ## Active production and ordering reality Lifecycle status is active — Siemens still produces this PM250 module, so it is a current BOM line, not a legacy part. ## Regulatory compliance documentation RoHS compliant since 18 May 2016, and REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w — the supplier provides the declaration of compliance with the order. Export control is AL N / ECCN 9N9999, so no special license is needed for most destinations.","metaTitle":"Siemens 6SL3225-0BE33-7UA0 SINAMICS G120 PM250, 37 kW HO","metaDescription":"SINAMICS G120 Power Module PM250, 37 kW high overload, 45 kW light overload, 380-480 V, IP20, active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"title":"6SL3225-0BE33-7UA0","Group Code":"R220","description":"SINAMICS G120 POWER MODULE PM250 WITHOUT FILTER POSSIBILITY OF REGENERATION 3AC380-480V +10/-10% 47-63HZ OUTPUT HIGH OVERLOAD: 37KW FOR 200% 3S,150% 57S,100% 240S AMBIENT TEMP 0 TO +50 DEG C OUTPUT LIGHT OVERLOAD: 45KW FOR 150% 3S,110% 57S,100% 240S AMBIENT TEMP 0 TO +40 DEG C 499 X 275 X 204 (HXWXD), FSE PROTECTION IP20 WITHOUT CONTROL UNIT AND BOP","Product Group":"9784","Product class":"C: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.","Quantity Unit":"1 Piece","Product Family":"Power Modules","lifecycle_stage":"mature","Packaging Quantity":"1","Export Control Regulations":"AL : N / ECCN : 9N9999","Packaging dimensions (L x W x H)":"600.00 x 400.00 x 310.00 mm","Compliance with the substance restrictions according to RoHS directive":"Since: 18-05-16","REACH Art. 33 Duty to inform according to the current list of candidates":"Lead CAS-No. 7439-92-1 > 0,1 % (w / w)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$4,034.79","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=159186&mlfb=6SL3225-0BE33-7UA0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3225-0BE33-7UA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3225-0BE33-7UA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}