{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6SL3300-7TH41-3AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"6SL3300-7TH41-3AA0","canonicalUrl":"https://aoctrl.com/siemens/6SL3300-7TH41-3AA0","factsUrl":"https://aoctrl.com/api/mcp/products/6SL3300-7TH41-3AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SINAMICS S120 Active Interface Module for Active Line Module, 1100/1400 kW, 3AC 660-690 V, 50/60 Hz, 1270 A rated current, chassis unit IP00, internal air cooling, includes DRIVE-CLiQ cable.","salesMarkdown":"The Siemens 6SL3300-7TH41-3AA0 is a SINAMICS S120 Active Interface Module (AIM) paired with an Active Line Module (ALM) for 1100/1400 kW drives on 660-690 V three-phase mains. It handles 1270 A continuous line current in a chassis IP00 format with internal air cooling, and ships with the DRIVE-CLiQ cable for the control link. This is the interface that conditions the incoming supply for the ALM — without it, the line module has no feedback or precharge path. The 1270 A rating at 660-690 VAC sets the continuous current the AIM must pass between the mains and the ALM. For a 1400 kW drive on a 690 V line, that current aligns with the full-load draw of the inverter section. The IP00 chassis means it is a panel-mount unit — no enclosure, no touch protection — so it goes into a cabinet with adequate clearance and forced airflow. Internal air cooling handles the thermal load, but the cabinet must supply the air path; derate if ambient exceeds 40 °C. Siemens lists this AIM at a mature lifecycle stage — meaning it is a stable, long-running product, not newly introduced and not flagged for phase-out. No last-time-buy or successor has been announced through official channels. In a SINAMICS S120 common DC-bus configuration, the AIM sits between the mains filter and the ALM. It houses the precharging circuit, the line-side voltage sensing, and the DRIVE-CLiQ interface that reports back to the Control Unit. The DRIVE-CLiQ cable included with the module connects directly to the ALM's X1 port. Mount the AIM close to the ALM to keep the DC bus bars short; the chassis unit bolts into a standard 19-inch cabinet frame.","metaTitle":"Siemens 6SL3300-7TH41-3AA0 SINAMICS S120 Active Interface Mo","metaDescription":"Siemens 6SL3300-7TH41-3AA0 SINAMICS S120 Active Interface Module for Active Line Module 1100/1400kW, 3AC 660-690V, 1270A, IP00. Mature lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["AC Drive (VFD) 600V"],"specifications":{"lifecycle_stage":"mature"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=344398&mlfb=6SL3300-7TH41-3AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6SL3300-7TH41-3AA0/alternatives.json"},"ai":{"faq":[{"question":"What is 6SL3300-7TH41-3AA0 used for?","answer":"It is the Active Interface Module for a SINAMICS S120 Active Line Module rated 1100/1400 kW. It handles the precharge, line sensing, and DRIVE-CLiQ communication between the mains and the ALM, passing 1270 A continuous at 660-690 VAC."},{"question":"Where can I buy 6SL3300-7TH41-3AA0 and how is it quoted?","answer":"This module is sourced to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time on your required quantity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6SL3300-7TH41-3AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6SL3300-7TH41-3AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}