{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A12-30-10-84","brand":"ABB","brandSlug":"abb","productSlug":"A12-30-10-84","canonicalUrl":"https://aoctrl.com/abb/A12-30-10-84","factsUrl":"https://aoctrl.com/api/mcp/products/A12-30-10-84","rawCanonicalId":null},"summary":{"shortDescription":"ABB A-Line Series, A12 frame, IEC contactor, 3-pole, 25 A general purpose / 11 A motor current, 600 VAC rated, 120 VAC coil, DIN rail mount, with 1 N.O. auxiliary contact block.","salesMarkdown":"## 25 A frame, 11 A motor duty — what the ratings actually mean The A12-30-10-84: Rated 25 A general purpose and 11 A motor current at 600 VAC, 3-pole. The 11 A figure is the AC-3 switching current for standard squirrel-cage motors — that's the number that governs real motor starts, not the 25 A resistive rating. The 120 VAC coil pulls in on a standard North American control transformer; the A12 frame snaps onto DIN rail and accepts the A-line accessory range (aux contacts, mechanical interlocks, surge suppressors). ## Panel fit and the built-in auxiliary DIN rail mount, 3-pole, A12 frame. The integrated 1 N.O. auxiliary contact block saves a DIN slot and a wiring step — it feeds the PLC input or the run-status lamp without a separate add-on. The A-line family shares accessories across frame sizes, so spare aux blocks and coil surge suppressors stock across multiple panel builds. ## Sourcing and cross-reference note Quoted to order against your BOM quantity. The AF series uses a different coil technology (electronic wide-range coil) versus the conventional 120 VAC coil on the A12-30-10-84. Panel rewiring is likely needed if swapping series. No direct drop-in guarantee without checking the coil circuit and the mounting footprint.","metaTitle":"ABB A12-30-10-84 Contactor, 25 A, 600 VAC, 3-Pole, DIN Rail","metaDescription":"ABB A12-30-10-84 IEC contactor, 25 A general purpose / 11 A motor, 120 VAC coil, 3-pole, DIN rail mount. EOL hot phase - sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Amps":"25","Size":"A12","Poles":"3","title":"A12-30-10-84","Mounting":"DIN Rail","Volts AC":"600","description":"Contactor, 11A, 3P, 600VAC, IEC, 120VAC Coil|11 Motor Current Amp, 25 General Purpose Amp, 600V Rated, 120V AC Coil. A-Line Series, A12 Frame, 3-Pole, IEC Contactor with 1 N.O. Auxiliary Contact Block.","Family / Style":"A-Line","lifecycle_stage":"eol_hot","Volts AC Control":"120"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$69.85","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ce24883bdf9b77875f002da789a30c44.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What are the key ratings of the A12-30-10-84?","answer":"25 A general purpose, 11 A motor current (AC-3), 600 VAC rated, 3-pole, 120 VAC coil, DIN rail mount. The A12 frame includes one built-in N.O. auxiliary contact."},{"question":"Will the A12-30-10-84 replace the 1SBL136061R2110 without rewiring?","answer":"Not directly. The 1SBL136061R2110 is an AF-series contactor with a wide-range electronic coil; the A12-30-10-84 uses a conventional 120 VAC coil. The coil circuit and possibly the mounting accessory layout differ. Verify the control voltage and the panel wiring before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/A12-30-10-84","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/A12-30-10-84 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}