{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A30-30-10-84","brand":"ABB","brandSlug":"abb","productSlug":"A30-30-10-84","canonicalUrl":"https://aoctrl.com/abb/A30-30-10-84","factsUrl":"https://aoctrl.com/api/mcp/products/A30-30-10-84","rawCanonicalId":null},"summary":{"shortDescription":"Eaton A30-30-10-84 IEC contactor, A30 frame, 3-pole, 34 A motor full-load current, 32 A general-purpose, 600 V rated, 120 V AC coil, 1 N.O. auxiliary contact block.","salesMarkdown":"## What the 34 A rating means for your motor circuit The A30-30-10-84: The 34 A figure is the motor full-load current (FLC) rating under IEC duty — this is the number that sizes the contactor for the load, not the 32 A general-purpose ampacity. For a three-phase motor at 460 V, 34 A FLC corresponds to roughly 25–30 HP, depending on the motor efficiency and service factor. The 32 A general-purpose rating applies to resistive or lightly inductive loads; for motor starting, use the 34 A FLC column. The 120 V AC coil matches a standard control transformer secondary or a 120 V relay output from a PLC. Coil inrush at pickup is roughly 7–10× the sealed VA, so the control transformer must be sized for the momentary draw of all contactors pulling in simultaneously. ## Lifecycle reality — end-of-life, sourced through surplus channels For a BOM that requires this exact form factor and auxiliary contact arrangement, the surplus channel is the only practical source. If the panel design allows a footprint change, a current-production Eaton contactor in the same current class (e.g., the XT series) would be the conventional replacement, but that requires a board or panel layout revision. ## Panel integration — what fits alongside it The A30 frame is a standard IEC contactor footprint that mounts on a DIN rail or with screws to a backplate. The 1 N.O. auxiliary contact block is built into the front — no add-on module needed for a single feedback signal to the PLC or a holding-circuit interlock. The 3-pole main contacts switch the three motor phases; the auxiliary switches independently at the same 600 V rating. In a panel with multiple contactors, the A30 frame's width and depth are consistent with other Eaton A-Line series sizes, so the DIN-rail pitch and the gland-plate layout stay uniform across the assembly. The 120 V AC coil draw is within the range of a standard 100 VA control transformer for a small panel with two or three contactors.","metaTitle":"A30-30-10-84 Eaton Contactor, 34 A, 3-Pole, 120 VAC Coil","metaDescription":"Eaton A30-30-10-84 IEC contactor, 34 A motor rating, 3-pole, 120 VAC coil, 1 N.O. auxiliary. End-of-life — sourced to order via independent distribution.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Amps":"34","Type":"Contactor","Poles":"3","title":"A30-30-10-84","description":"Contactor, 32A, 3P, 600VAC, IEC, 120VAC Coil|34 Motor Current Amp, 50 General Purpose Amp, 600V Rated, 120V AC Coil. A-Line Series, A30 Frame, 3-Pole, IEC Contactor with 1 N.O. Auxiliary Contact Block.","lifecycle_stage":"eol_hot","Volts AC Control":"120"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$707.02","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ce24883bdf9b77875f002da789a30c44.pdf","sourceUrl":null},"ai":{"faq":[{"question":"What is the difference between the 34 A motor rating and the 32 A general-purpose rating on this contactor?","answer":"The 34 A figure is the motor full-load current (FLC) rating per IEC utilization category AC-3 — this is the current the contactor can switch during motor starting and running without excessive contact wear. The 32 A general-purpose rating (AC-1) applies to resistive or lightly inductive loads where the inrush is minimal. For a motor circuit, always use the 34 A FLC column for sizing."},{"question":"What compliance documentation is available for the A30-30-10-84?","answer":"The A30-30-10-84 is an IEC-rated contactor. Eaton typically provides CE marking, RoHS compliance, and UL/CSA recognition for the A-Line series. Specific declaration-of-conformity documents and the product drawing with approvals are available upon request at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/A30-30-10-84","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/A30-30-10-84 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}