{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C15183","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C15183","canonicalUrl":"https://aoctrl.com/schneider/A9C15183","factsUrl":"https://aoctrl.com/api/mcp/products/A9C15183","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 CT contactor, A9C15183, 2P, 25 A AC-7A rated operational current, 230 V AC 50 Hz control voltage, clip-on DIN rail mount, IP20.","salesMarkdown":"## Acti9 CT Contactor – A9C15183 It clips onto a 35 mm symmetrical DIN rail and occupies 2 x 9 mm pitches (18 mm wide), so it fits neatly into a compact modular enclosure alongside other Acti9 devices. Rated operational current is 25 A in AC-7A category and 8.5 A in AC-7B — the AC-7A figure governs resistive loads like lighting or heating, while AC-7B covers inductive loads typical of small motors. Control voltage is 230 V AC at 50 Hz, with an inrush of 15 VA and a hold-in draw of 3.8 VA. For motor loads, the AC-7B rating of 8.5 A is the figure to use — that's the inductive switching capacity. The 230 V AC control coil is standard for European panel builds, and the 50/60 Hz tolerance means it works on both common mains frequencies. Pollution degree 2 is the typical industrial environment where only non-conductive pollution occurs, with occasional condensation. The 18 mm width (2 x 9 mm pitches) matches the Acti9 modular system, so it aligns with MCBs, RCDs, and other Acti9 devices on the same rail. Power circuit terminals are tunnel type: accept up to 2 x 2.5 mm² flexible or 1 x 6 mm² rigid. Control circuit terminals take 2 x 2.5 mm² flexible or 2 x 1.5 mm² rigid. Wire stripping length is 10 mm, tightening torque 0.8 N·m. The 2 NO pole contact composition gives two normally-open main contacts.","metaTitle":"A9C15183 Acti9 CT Contactor, 2P, 25 A, 230 V AC","metaDescription":"Schneider Electric A9C15183 Acti9 CT contactor, 2 poles, 25 A AC-7A rated operational current, 230 V AC control voltage. Current production. Clip-on DIN rail mount. IEC/EN 61095.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"66 mm","Poles":"2P","Width":"18 mm","Height":"90 mm","Current":"25 A AC-7 A 8.5 A AC-7B","Voltage":"250 V AC 50 Hz","Frequency":"100 switching operations/day","Application":"Control circuit","Coil Voltage":"230 V AC 50 Hz","Control Type":"Remote and manual control","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"60 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Control Signal Type":"Maintained","Temperature Storage":"-40...60 °C","Utilization Category":"AC-1 conforming to IEC 60947-4","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9C15183/contactor-with-manual-control-ctc40-2-no-25-a-230-v-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C15183/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C15183","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C15183 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}