{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C15509","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C15509","canonicalUrl":"https://aoctrl.com/schneider/A9C15509","factsUrl":"https://aoctrl.com/api/mcp/products/A9C15509","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 TL40 impulse relay, A9C15509, 2P, 16 A rated, 230 V AC control, DIN rail mount.","salesMarkdown":"It is rated 16 A at 250 V AC, 50 Hz, with 2 normally-open poles (2 NO). Control is via a 230 V AC impulse (50 Hz), minimum 50 ms duration, from a remote push-button or PLC output drawing 3 mA. The 16 A rated current (In) at 250 V AC is the continuous thermal current the contacts can carry in resistive or general-use AC loads (AC-22 duty). Electrical durability is 200,000 cycles under AC-22 — that is the service life for switching resistive loads like lighting banks or heating elements. For motor or inductive loads, derate accordingly; the relay is not rated for AC-3 motor switching. The 2-pole configuration (2 NO) means both poles switch simultaneously, suitable for two-wire or two-phase circuits up to 250 V line-to-neutral. Width is 18 mm (1 module), depth 69 mm, height 87 mm — fits a standard 1-module cutout in a distribution board. Terminals are tunnel type: power circuit accepts 1 to 4 mm² rigid or flexible (1 or 2 cables), control circuit 0.5 to 1.5 mm². Strip length 9 mm, tightening torque 1 N·m. IP20 on the opening (finger-safe), IP40 inside an enclosure — suitable for clean, dry indoor panels. Pollution degree 3 (industrial environment). Compliant with IEC 60669-1 and IEC 60669-2-2 (switches for household and similar fixed electrical installations — particular requirements for electromagnetic remote-control switches). Rated insulation voltage (Ui) 500 V AC, impulse withstand voltage (Uimp) 2.5 kV. NF quality label. Ambient operating temperature -20 to 50 °C, storage -40 to 80 °C. Relative humidity 95% at 55 °C.","metaTitle":"Schneider Electric A9C15509 Acti9 TL40 Impulse Relay, 16 A,","metaDescription":"Schneider Electric A9C15509 Acti9 TL40 impulse relay, 16 A rated current, 2 poles, 230 V AC control. DIN rail mount, IEC 60669 compliant. Current production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"69 mm","Poles":"2P","Width":"18 mm","Height":"87 mm","Standards":"IEC 60669-1 IEC 60669-2-2","Noise level":"60 dB","9 Mm Pitches":"2","Control type":"Remote and manual control","Network type":"AC","Product name":"Acti9 TL40","Mounting mode":"Fixed","Quality labels":"NF","lifecycle_stage":"current","Impulse duration":"50 ms","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"3","Range Of Product":"Acti9","Device short name":"TL40","Network frequency":"50 Hz","Relative humidity":"95 % at 55 °C","Tightening torque":"1 N.m","Device application":"Standard","[In] rated current":"16 A","Control signal type":"Impulse","Remote control type":"Illuminated push-button 3 mA","Switching frequency":"5 switching operations/minute","Electrical durability":"AC-22: 200000 cycles","Wire stripping length":"9 mm","Connections - terminals":"Power circuit: tunnel type terminals 1 cable(s) 1...4 mm² rigid Power circuit: tunnel type terminals 2 cable(s) 1...2.5 mm² rigid Power circuit: tunnel type terminals 1 cable(s) 1...4 mm² flexible Power circuit: tunnel type terminals 2 cable(s) 1...2.5 mm² flexible Control circuit: tunnel type terminals 1 cable(s) 0.5...1.5 mm² rigid Control circuit: tunnel type terminals 1 cable(s) 0.5...1.5 mm² flexible Power circuit: tunnel type terminals 1 cable(s) 1...4 mm² flexible with ferrule Power circuit: tunnel type terminals 2 cable(s) 1...2.5 mm² flexible with ferrule Control circuit: tunnel type terminals 1 cable(s) 0.5...1.5 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 (on opening) IP40 conforming to IEC 60529 (in enclosure)","Pole contact composition":"2 NO","Product or component type":"Impulse relay","[Uc] control circuit voltage":"230 V AC 50 Hz","[Ui] rated insulation voltage":"500 V AC","[Ue] rated operational voltage":"250 V AC 50 Hz","Hold-in power consumption in VA":"19 VA","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-20...50 °C","[Uimp] rated impulse withstand voltage":"2.5 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$73.39","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9C15509/impulse-relay-acti9-tl40-2p-1no-16-a-230-v-ac-50-hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C15509/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the A9C15509?","answer":"Rated current 16 A at 250 V AC, 2 poles (2 NO), control voltage 230 V AC 50 Hz, electrical durability 200,000 cycles under AC-22. DIN rail mount, width 18 mm."},{"question":"What compliance standards does the A9C15509 meet?","answer":"It complies with IEC 60669-1 and IEC 60669-2-2. Rated insulation voltage 500 V AC, impulse withstand 2.5 kV. NF quality label."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C15509","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C15509 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}