{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C20443","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C20443","canonicalUrl":"https://aoctrl.com/schneider/A9C20443","factsUrl":"https://aoctrl.com/api/mcp/products/A9C20443","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iCT contactor, A9C20443, 3P, 40 A AC-7A / 15 A AC-7B, 127 V AC 60 Hz coil, clip-on 35 mm DIN rail, IP20.","salesMarkdown":"It is rated for a 127 V AC 60 Hz maintained control signal and carries a 40 A AC-7A and 15 A AC-7B operational current at 400 V AC 60 Hz, per IEC/EN 61095. The AC-7A rating covers resistive and inductive loads typical of lighting and heating; the AC-7B rating covers motor loads up to 15 A. This means the contactor is sized for a 3.5 kW motor at 400 V (roughly 7.5 A full-load) with headroom on the resistive side. ## Durability and switching life Electrical durability is rated per duty: 100,000 cycles at 40 A AC-7A, 30,000 cycles at 15 A AC-7B, and 30,000 cycles for AC-3 motor switching. Mechanical durability is 1,000,000 cycles. The switching frequency is limited to 100 operations per day, which is typical for contactors in building-services duty — not for high-speed machine cycling. Dimensions: 85 mm high, 54 mm wide, 68.5 mm deep. The 54 mm width is 3 module pitches (9 mm each). Power circuit terminals accept 6 to 25 mm² rigid or 6 to 16 mm² flexible cable; control circuit terminals accept 1.5 to 2.5 mm². Tightening torque: 3.5 N·m for power, 0.8 N·m for control. IP20 on the body, IP40 in a modular enclosure. Tropicalisation conforms to EN 60947-4-1 and EN 61095.","metaTitle":"Schneider Electric A9C20443 Acti9 iCT Contactor, 40 A AC-7A,","metaDescription":"Schneider Electric A9C20443 Acti9 iCT contactor. 3P, 40 A AC-7A / 15 A AC-7B, 127 V AC 60 Hz coil. IEC/EN 61095. Clip-on 35 mm DIN rail. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"68.5 mm","Poles":"3P","Width":"54 mm","Height":"85 mm","Current":"40 A AC-7 A 15 A AC-7B","Voltage":"400 V AC 60 Hz","Frequency":"100 switching operations/day","Application":"Motor-heating-lighting","Coil Voltage":"127 V AC 60 Hz","Control Type":"Remote control","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Control Signal Type":"Maintained","Temperature Storage":"-40...70 °C","Electrical Life Cycles":"100000 cycles IEC/EN 61095 40 A 60 Hz AC-7 A 30000 cycles IEC/EN 61095 15 A 60 Hz AC-7B 30000 cycles IEC/EN 61095 60 Hz AC-7C 100000 cycles EN/IEC 60947-4-1 60 Hz AC-1 30000 cycles EN/IEC 60947-4-1 60 Hz AC-3 30000 cycles EN/IEC 60947-4-1 60 Hz AC-5 a 30000 cycles EN/IEC 60947-4-1 60 Hz AC-5b","Mechanical Life Cycles":"1000000 cycles","Main Product Or Component Type":"Contactor","Ambient Air Temperature Operation":"-5...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9C20443/ict-40a-3no-127v-60hz-contactor/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C20443/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C20443","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C20443 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}