{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C61340","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C61340","canonicalUrl":"https://aoctrl.com/schneider/A9C61340","factsUrl":"https://aoctrl.com/api/mcp/products/A9C61340","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N integrated control MCB, A9C61340, 40 A, 3P, curve B, 20 kA breaking capacity, 230 V AC control.","salesMarkdown":"The 20 kA breaking capacity at 230 V AC (10 kA at 380–415 V) means it can safely interrupt a serious fault without upstream devices having to clear it. The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC, and supports maintained, impulse, or toggle commands. That's the flexibility you need when tying into a PLC output or a manual pushbutton station — no extra interface relay required for most common signal levels. Takes 11 x 9 mm pitches of rail space — call it 99 mm wide, 84 mm tall, 77 mm deep. That's a standard 3-module footprint for the Acti9 family, so it slots into a distribution board without surprises. IP20 rated, so it's for inside an enclosure, not on the wet side of the panel door. The tropicalisation class 2 adds some margin for high-humidity storage or operation — 93% RH at 40 °C is the listed limit. The B curve means the magnetic trip threshold is 3–5 times rated current (120–200 A for this 40 A unit). That's the standard choice for general distribution and control circuits — it won't false-trip on motor inrush, but it clears fast on a hard short. The thermal-magnetic trip technology is the workhorse for this class; no electronics to fail, no auxiliary power needed for the protection function. Electrical durability is 50,000 cycles under AC-1 resistive load at 50 Hz. That's the same as the mechanical endurance, so the switch mechanism is the limiting factor, not the contacts. For a control breaker that sees daily remote switching, that's a solid service life before you'd plan a replacement.","metaTitle":"Schneider Electric A9C61340 Reflex iC60N 40A 3P Curve B MCB","metaDescription":"Schneider Electric A9C61340 Reflex iC60N integrated control MCB, 40 A, 3-pole, curve B, 20 kA breaking capacity at 230 V AC. Active lifecycle, sourced to order. Fit for control and","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"77 mm","Range":"Acti9","Width":"99 mm","Colour":"White","Height":"84 mm","Curve code":"B","9 Mm Pitches":"11","Control type":"Remote control by continuous command Remote control by pulse ON/OFF button Toggle","Network type":"AC","Product name":"Reflex iC60","Mounting mode":"Fixed","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"Green LED: device ON Flashing LED: device overheat Flashing LED: device tripped Flashing LED: device ready Red LED: fault","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3","Breaking capacity":"20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"Reflex iC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"93 % at 40 °C","Device application":"Control Distribution","[In] rated current":"40 A","Control signal type":"Maintained Impulse Maintained very low voltage","Trip unit technology":"Thermal-magnetic","Electrical durability":"AC-1: 50000 cycles AC 50 Hz","Mechanical durability":"50000 cycles","Breaking capacity code":"N","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"3","Product or component type":"Integrated control circuit breaker","[Us] rated supply voltage":"230 V AC at 50/60 Hz","Contact position indicator":"Yes","Locking options description":"Padlock in OFF position","[Uc] control circuit voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","[Ui] rated insulation voltage":"500 V AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9C61340/reflex-ic60n-ti24-40-a-3p-curve-b-integrated-control-mcb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C61340/alternatives.json"},"ai":{"faq":[{"question":"What control voltages does the A9C61340 accept?","answer":"The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC. It supports maintained, impulse, and toggle command types, so it works with most PLC outputs, pushbuttons, or remote control systems without an extra interface relay."},{"question":"What is the breaking capacity of the A9C61340?","answer":"It's rated 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, both conforming to EN/IEC 60947-2. That's the N breaking capacity code in the Reflex iC60N range — sufficient for most distribution board applications where the upstream transformer limits fault current."},{"question":"What does the local signalling on the A9C61340 indicate?","answer":"A green LED shows the device is ON. A flashing LED indicates overheat, tripped, or ready status depending on the flash pattern. A red LED signals a fault. This gives you a quick visual check at the panel without needing a multimeter."},{"question":"What compliance documentation is available for the A9C61340?","answer":"The breaking capacity is certified to EN/IEC 60947-2. The IP20 rating conforms to IEC 60529. The part is part of the Schneider Acti9 range, which typically carries CE, UKCA, and EAC markings for European and Eurasian markets. For specific RoHS, REACH, or UL documentation, the manufacturer's product page or your distributor can provide the declaration of conformity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C61340","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C61340 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}