{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C62216","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C62216","canonicalUrl":"https://aoctrl.com/schneider/A9C62216","factsUrl":"https://aoctrl.com/api/mcp/products/A9C62216","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N, integrated control circuit breaker, 16 A, 2P, curve C, 20 kA breaking capacity.","salesMarkdown":"The Schneider Electric A9C62216 is a Reflex iC60N integrated control circuit breaker — a thermal-magnetic MCB with a built-in control function, so it both protects the circuit and acts as a remotely operated switch. The 2-pole version (2P) protects both phase and neutral on a single-phase 230 V AC network. Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, per EN/IEC 60947-2. The N breaking capacity code tells you it's the standard-interrupting version in the iC60 family, not the high-performance H or L variants. Mounts on a 35 mm symmetrical DIN rail, fixed position, occupying 9 module pitches (9 x 9 mm = 81 mm width). That's a standard footprint for a 2P MCB with integrated control, so it slots into any DIN-rail enclosure without special adapters. The white housing and IP20 finger-safe terminals are standard for panel-mounted distribution gear. Control voltage options cover both AC and DC: 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC. The control signal can be maintained (continuous command), maintained very low voltage, or impulse (pulse). That flexibility lets you wire it to a PLC digital output, a pushbutton station, or a remote SCADA contact — no separate contactor needed for the switching function. Local signalling includes a red LED for fault, green LED for device ON, and flashing patterns for device ready, tripped, or overheat. This is useful for panel troubleshooting — you can read the breaker's state at a glance without a meter. ## Sourcing and lifecycle — current production, no obsolescence risk The part belongs to the Acti9 range and the Reflex iC60N sub-family, which is a well-established platform with broad global approvals. Pollution degree 3 (industrial environment), tropicalisation class 2, and 93% relative humidity at 40 °C — all point to reliable operation in non-conditioned panel environments.","metaTitle":"Schneider Electric A9C62216 Reflex iC60N, 16 A, 2P, Curve C","metaDescription":"Schneider Electric A9C62216 Reflex iC60N integrated control MCB, 16 A rated current, 2 poles, curve C, 20 kA breaking capacity at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"77 mm","Width":"81 mm","Height":"84 mm","IP Rating":"IP20","Application":"Control Distribution","Coil Voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3","Insulation Voltage Ui":"500 V AC","Electrical Life Cycles":"AC-1: 50000 cycles AC 50 Hz","Mechanical Life Cycles":"50000 cycles","Main Product Or Component Type":"Integrated control circuit breaker"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$406.86","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/id/en/product/A9C62216/reflex-ic60n-ti24-16-a-2p-curve-c-integrated-control-mcb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C62216/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C62216","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C62216 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}