{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C62310","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C62310","canonicalUrl":"https://aoctrl.com/schneider/A9C62310","factsUrl":"https://aoctrl.com/api/mcp/products/A9C62310","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N integrated control circuit breaker, 10 A, 3P, curve C, 20 kA breaking capacity.","salesMarkdown":"It combines overcurrent protection with remote switching in a single 3-pole unit, rated at 10 A with a C trip curve. The thermal-magnetic trip handles distribution and control panel loads, while the integrated control coil allows remote ON/OFF via maintained or impulse signals at 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC. ## Breaking capacity and fault clearing Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, both per EN/IEC 60947-2. That means it clears high fault currents on a 230 V distribution bus without upstream coordination headaches. The N breaking capacity code places it in the standard-duty tier for commercial and light industrial panels. Dimensions are 99 mm wide by 84 mm high by 77 mm deep, occupying 11 DIN pitches. That's a standard 3-pole MCB footprint — no surprises for a panel layout. ## Control and signaling The control circuit accepts multiple voltage options — 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC — with maintained or impulse commands. Local signaling uses a multi-color LED: green for ON, flashing for device ready or tripped, red for fault. A contact position indicator and padlock provision in the OFF position add safety for lockout/tagout. ## Durability and environmental specs Rated for 50,000 electrical cycles under AC-1 resistive load and 50,000 mechanical cycles. Tropicalisation class 2 and 93% relative humidity at 40 °C mean it handles coastal or unconditioned plant environments.","metaTitle":"Schneider Electric A9C62310 Reflex iC60N, 10A 3P C-curve MCB","metaDescription":"Schneider Electric A9C62310 Reflex iC60N integrated control MCB. 10 A rated, 3-pole, C-curve, 20 kA breaking capacity at 230 V. Active production. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White","Depth":"77 mm","Width":"99 mm","Height":"84 mm","IP Rating":"IP20","Application":"Distribution Control","Coil Voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3","Breaking Capacity":"20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Insulation Voltage Ui":"500 V AC","Electrical Life Cycles":"AC-1: 50000 cycles AC 50 Hz","Mechanical Life Cycles":"50000 cycles","Main Product Or Component Type":"Integrated control circuit breaker"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$419.06","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9C62310/reflex-ic60n-ti24-10-a-3p-curve-c-integrated-control-mcb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C62310/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C62310","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C62310 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}