{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C62316","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C62316","canonicalUrl":"https://aoctrl.com/schneider/A9C62316","factsUrl":"https://aoctrl.com/api/mcp/products/A9C62316","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N integrated control circuit breaker, A9C62316, 16 A, 3P, curve C, 20 kA breaking capacity, 230 V AC control.","salesMarkdown":"The 3-pole version handles three-phase circuits, and the thermal-magnetic trip unit responds to both overload and short-circuit conditions. Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, both per EN/IEC 60947-2. The N breaking capacity code places it in the standard-duty tier for this platform. Control voltage options cover 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC, with a choice of maintained or impulse signal types. This flexibility lets the same unit work across building management systems (24 V DC) or direct 230 V AC relay outputs from a PLC. The local signalling LED reports device ON, tripped, overheat, or fault state — useful during commissioning or fault-finding without a meter. Fixed mounting mode; no plug-in base. Dimensions are 99 mm wide by 84 mm high by 77 mm deep — 11 modules of 9 mm pitch, so it occupies 11 DIN spaces. IP20 finger-safe terminals are standard for enclosed panels; pollution degree 3 means it tolerates conductive pollution typical of industrial control rooms. Padlockable in the OFF position for lockout/tagout. Earth-leakage protection requires a separate add-on block — not integral.","metaTitle":"Schneider Electric A9C62316 Reflex iC60N, 16 A, 3P, Curve C,","metaDescription":"Schneider Electric A9C62316 Reflex iC60N integrated control MCB, 16 A, 3P, curve C, 20 kA breaking capacity at 230 V. Active production, sourced to order. DIN rail mount, IP20.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"77 mm","Range":"Acti9","Width":"99 mm","title":"A9C62316","Colour":"White","Height":"84 mm","Curve code":"C","description":"Reflex iC60N Ti24 16 A 3P curve C integrated control MCB","9 Mm Pitches":"11","Control type":"Remote control by pulse Remote control by continuous command Toggle ON/OFF button","Network type":"AC","Product name":"Reflex iC60","Mounting mode":"Fixed","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"Green LED: device ON Flashing LED: device tripped Flashing LED: device overheat Red LED: fault Flashing LED: device ready","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3","Breaking capacity":"20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"Reflex iC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"93 % at 40 °C","Device application":"Control Distribution","[In] rated current":"16 A","Control signal type":"Maintained very low voltage Maintained Impulse","Trip unit technology":"Thermal-magnetic","Electrical durability":"AC-1: 50000 cycles AC 50 Hz","Mechanical durability":"50000 cycles","Breaking capacity code":"N","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"3","Product or component type":"Integrated control circuit breaker","[Us] rated supply voltage":"230 V AC at 50/60 Hz","Contact position indicator":"Yes","Locking options description":"Padlock in OFF position","[Uc] control circuit voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","[Ui] rated insulation voltage":"500 V AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9C62316/reflex-ic60n-ti24-16-a-3p-curve-c-integrated-control-mcb/"},"ai":{"faq":[{"question":"What breaking capacity does the A9C62316 have at 230 V and 400 V?","answer":"At 220–240 V AC the Icu is 20 kA; at 380–415 V AC it is 10 kA, both per EN/IEC 60947-2. That 10 kA at 400 V is the figure to use for selectivity studies on a 400 V three-phase distribution board."},{"question":"What control voltages can I use on the A9C62316?","answer":"The coil accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC. Signal types include maintained (continuous) and impulse (pulse) commands. Verify your control circuit voltage before ordering — the 24 V DC option is common for PLC outputs, while 230 V AC suits direct building-management relay contacts."},{"question":"Does the A9C62316 include earth-leakage protection?","answer":"No. Earth-leakage protection is handled by a separate add-on block (not included). The breaker itself provides thermal-magnetic overcurrent protection only."},{"question":"What is the physical size and mounting of the A9C62316?","answer":"It is 99 mm wide (11 modules of 9 mm pitch), 84 mm high, 77 mm deep. Mounts on a 35 mm symmetrical DIN rail. IP20 rated, padlockable in OFF position."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C62316","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C62316 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}