{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C62340","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C62340","canonicalUrl":"https://aoctrl.com/schneider/A9C62340","factsUrl":"https://aoctrl.com/api/mcp/products/A9C62340","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N, integrated control MCB, A9C62340, 40 A, 3P, curve C, 20 kA breaking capacity.","salesMarkdown":"It combines overcurrent protection with remote control switching in a single 3-pole unit, rated at 40 A with a C trip curve. The thermal-magnetic trip unit handles overloads and short circuits, while the control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC for remote on/off commands via maintained or impulse signals. For motor or lighting circuits with inrush, the C curve means the magnetic trip fires at 5 to 10 times In — so a 40 A C-curve breaker holds through a 200–400 A surge long enough for a motor start or capacitor bank energization, but clears fast on a hard short. Breaking capacity is 20 kA Icu at 230 V AC and 10 kA Icu at 415 V AC, both per EN/IEC 60947-2. Three poles protected (3P) means all three phases are switched and monitored. The control voltage options (230 V AC, 24 V AC, 48 V AC, 24 V DC, 48 V DC) give flexibility for different coil supplies — a 24 V DC control signal is common in PLC-driven panels, while 230 V AC suits direct line-voltage switching. Fixed mounting mode, 11 module pitches wide (9 mm per pitch = 99 mm width).","metaTitle":"Schneider Electric A9C62340 Reflex iC60N MCB, 40 A 3P Curve","metaDescription":"Schneider Electric A9C62340 Reflex iC60N integrated control circuit breaker. 40 A rated current, 3 poles, curve C, 20 kA breaking capacity at 230 V. Active production, DIN rail mou","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"77 mm","Range":"Acti9","Width":"99 mm","title":"A9C62340","Colour":"White","Height":"84 mm","Curve code":"C","description":"Reflex iC60N Ti24 40 A 3P curve C integrated control MCB","9 Mm Pitches":"11","Control type":"Remote control by continuous command Toggle Remote control by pulse ON/OFF button","Network type":"AC","Product name":"Reflex iC60","Mounting mode":"Fixed","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"Flashing LED: device overheat Flashing LED: device ready Red LED: fault Flashing LED: device tripped Green LED: device ON","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3","Breaking capacity":"20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"Reflex iC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"93 % at 40 °C","Device application":"Control Distribution","[In] rated current":"40 A","Control signal type":"Maintained Maintained very low voltage Impulse","Trip unit technology":"Thermal-magnetic","Electrical durability":"AC-1: 50000 cycles AC 50 Hz","Mechanical durability":"50000 cycles","Breaking capacity code":"N","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"3","Product or component type":"Integrated control circuit breaker","[Us] rated supply voltage":"230 V AC at 50/60 Hz","Contact position indicator":"Yes","Locking options description":"Padlock in OFF position","[Uc] control circuit voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","[Ui] rated insulation voltage":"500 V AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9C62340/reflex-ic60n-ti24-40-a-3p-curve-c-integrated-control-mcb/"},"ai":{"faq":[{"question":"What are the control voltage options for this breaker?","answer":"The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC. The control type supports maintained signal, maintained very low voltage, and impulse (pulse) commands."},{"question":"What does the C curve mean on this 40 A breaker?","answer":"The C curve means the magnetic trip threshold is 5 to 10 times the rated current — so for a 40 A breaker, the instantaneous trip activates between 200 A and 400 A. This suits circuits with moderate inrush like lighting banks, small motors, or transformers."},{"question":"What approvals or standards does this part comply with?","answer":"The breaking capacity is certified to EN/IEC 60947-2. IP20 per IEC 60529. Pollution degree 3 per IEC 60664. Tropicalisation class 2 is specified. The part is from the Acti9 range, which carries Schneider's standard CE and other applicable markings for European markets."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C62340","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C62340 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}