{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C63216","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C63216","canonicalUrl":"https://aoctrl.com/schneider/A9C63216","factsUrl":"https://aoctrl.com/api/mcp/products/A9C63216","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N Ti24, integrated control MCB, 16 A, 2P, curve D, 20 kA Icu at 230 V AC.","salesMarkdown":"The thermal-magnetic trip handles overloads (thermal) and short circuits (magnetic) in one device. Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, per EN/IEC 60947-2. Control voltage options cover 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — so it fits both AC and DC control circuits common in panel designs. The control signal can be maintained (continuous command), maintained very low voltage, or impulse (pulse). Electrical durability is 50,000 cycles under AC-1 resistive load at 50 Hz — that's the expected life before contact wear becomes a concern. Mechanical durability matches at 50,000 cycles. The 2-pole body takes 9 module pitches (9 x 9 mm = 81 mm width), so plan for 81 mm of DIN rail space per unit. Depth is 77 mm, height 84 mm — fits standard distribution boards with adequate wiring gutter. Local signalling includes a flashing LED for device ready, green for ON, flashing for overheat, red for fault, and flashing for tripped — useful for quick fault isolation on the panel door.","metaTitle":"Schneider Electric A9C63216 Reflex iC60N Ti24 16 A 2P curve","metaDescription":"Schneider Electric A9C63216 Reflex iC60N integrated control MCB, 16 A, 2P, curve D, 20 kA breaking capacity at 230 V AC. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"77 mm","Range":"Acti9","Width":"81 mm","Colour":"White","Height":"84 mm","Curve code":"D","9 Mm Pitches":"9","Control type":"Remote control by continuous command Toggle ON/OFF button Remote control by pulse","Network type":"AC","Product name":"Reflex iC60","Mounting mode":"Fixed","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"Flashing LED: device ready Green LED: device ON Flashing LED: device overheat Red LED: fault Flashing LED: device tripped","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3","Breaking capacity":"20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"Reflex iC60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"93 % at 40 °C","Device application":"Distribution Control","[In] rated current":"16 A","Control signal type":"Maintained Maintained very low voltage Impulse","Trip unit technology":"Thermal-magnetic","Electrical durability":"AC-1: 50000 cycles AC 50 Hz","Mechanical durability":"50000 cycles","Breaking capacity code":"N","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"2","Product or component type":"Integrated control circuit breaker","[Us] rated supply voltage":"230 V AC at 50/60 Hz","Contact position indicator":"Yes","Locking options description":"Padlock in OFF position","[Uc] control circuit voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","[Ui] rated insulation voltage":"500 V AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$364.76","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9C63216/reflex-ic60n-ti24-16-a-2p-curve-d-integrated-control-mcb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C63216/alternatives.json"},"ai":{"faq":[{"question":"What control voltages does the A9C63216 accept?","answer":"The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC. The control signal type can be maintained (continuous), maintained very low voltage, or impulse."},{"question":"What is the breaking capacity of the A9C63216?","answer":"20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, both conforming to EN/IEC 60947-2."},{"question":"What is the physical size of the A9C63216?","answer":"Width 81 mm (9 module pitches), height 84 mm, depth 77 mm. It mounts on a 35 mm symmetrical DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C63216","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C63216 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}