{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C63225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C63225","canonicalUrl":"https://aoctrl.com/schneider/A9C63225","factsUrl":"https://aoctrl.com/api/mcp/products/A9C63225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N, integrated control circuit breaker, 25 A, 2P, curve D, 20 kA breaking capacity at 240 V AC.","salesMarkdown":"The 2-pole version breaks both line and neutral, which matters when the neutral is not bonded to earth downstream. The IP20 finger-safe terminals are fine for enclosed panels; if the breaker lives near a washdown zone, it needs a separate enclosure. Rated 20 kA Icu at 220…240 V AC and 10 kA Icu at 380…415 V AC, both per EN/IEC 60947-2 — that is the maximum fault current the breaker can safely interrupt without welding contacts or rupturing the case. The 'N' in iC60N designates the N breaking capacity class, which is the standard industrial grade for this platform. ## Control flexibility and integration into a circuit The control circuit accepts multiple signal types: impulse (momentary pushbutton), maintained (latching contact), or maintained very low voltage (24 V DC or 24 V AC). The control voltage options cover 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — so it works with both line-voltage pilot devices and low-voltage PLC or relay outputs. The toggle and ON/OFF button on the front give local manual override, and the padlock provision (OFF position only) lets a lockout/tagout program secure the circuit during maintenance. ## Environmental and durability ratings Tropicalisation class 2 means the breaker is treated against moisture and fungal growth for use in warm, humid climates. Electrical durability is 50,000 cycles at AC-1 (resistive load), mechanical durability the same 50,000 cycles — that is a solid service life for a control breaker that cycles daily. Relative humidity tolerance of 93 % at 40 °C covers most non-condensing indoor environments. The thermal-magnetic trip unit provides both overload (thermal bimetal) and short-circuit (magnetic coil) protection, with the D curve's magnetic trip threshold at 10–20× In, which is why it is chosen for motor and transformer starting duty.","metaTitle":"Schneider Electric A9C63225 Reflex iC60N, 25 A, 2P, Curve D","metaDescription":"Schneider Electric A9C63225 Reflex iC60N integrated control MCB, 25 A, 2P, curve D, 20 kA breaking capacity at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"77 mm","Width":"81 mm","Height":"84 mm","IP Rating":"IP20","Application":"Control Distribution","Coil Voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3","Insulation Voltage Ui":"500 V AC","Electrical Life Cycles":"AC-1: 50000 cycles AC 50 Hz","Mechanical Life Cycles":"50000 cycles","Main Product Or Component Type":"Integrated control circuit breaker"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$374.24","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/mk/en/product/A9C63225/reflex-ic60n-ti24-25-a-2p-curve-d-integrated-control-mcb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C63225/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C63225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C63225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}