{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C63310","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C63310","canonicalUrl":"https://aoctrl.com/schneider/A9C63310","factsUrl":"https://aoctrl.com/api/mcp/products/A9C63310","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60N, integrated control MCB, 10 A, 3P, curve D, 20 kA breaking capacity at 240 V AC.","salesMarkdown":"The thermal-magnetic trip unit handles both overload and short-circuit protection. Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, per EN/IEC 60947-2. The 3-pole version here (3P) protects three phases simultaneously. ## Control and signalling This isn't just a breaker — it's a remotely controllable switch. Control voltage options include 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC, with pulse or maintained command types. That means you can wire it to a PLC output or a remote pushbutton station to cycle the load without climbing into the panel. Local signalling uses a multi-colour LED: green for ON, flashing for tripped or overheat conditions. The unit is padlockable in the OFF position, giving a positive lockout for maintenance. Contact position indicator is visible through the front bezel — no guessing whether it's open or closed. Dimensions are 99 mm wide (11 x 9 mm pitches), 84 mm high, 77 mm deep. IP20 rated, so it's for enclosed panels only, not washdown areas. Rated for 93% relative humidity at 40 °C, with tropicalisation class 2 — handles hot, humid plant floors without internal condensation issues.","metaTitle":"Schneider Electric A9C63310 Reflex iC60N, 10 A, 3P, Curve D,","metaDescription":"Schneider Electric A9C63310 Reflex iC60N integrated control MCB, 10 A rated, 3 poles, curve D, 20 kA breaking capacity at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"77 mm","Range":"Acti9","Width":"99 mm","Colour":"White","Height":"84 mm","Curve code":"D","9 Mm Pitches":"11","Control type":"Toggle Remote control by pulse ON/OFF button Remote control by continuous command","Network type":"AC","Product name":"Reflex iC60","Mounting mode":"Fixed","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"Flashing LED: device tripped Green LED: device ON Flashing LED: device ready Flashing LED: device overheat Red LED: fault","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3","Breaking capacity":"20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"Reflex iC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"93 % at 40 °C","Device application":"Control Distribution","[In] rated current":"10 A","Control signal type":"Maintained very low voltage Maintained Impulse","Trip unit technology":"Thermal-magnetic","Electrical durability":"AC-1: 50000 cycles AC 50 Hz","Mechanical durability":"50000 cycles","Breaking capacity code":"N","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"3","Product or component type":"Integrated control circuit breaker","[Us] rated supply voltage":"230 V AC at 50/60 Hz","Contact position indicator":"Yes","Locking options description":"Padlock in OFF position","[Uc] control circuit voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","[Ui] rated insulation voltage":"500 V AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9C63310/reflex-ic60n-ti24-10-a-3p-curve-d-integrated-control-mcb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C63310/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this Reflex iC60N?","answer":"Rated current 10 A, curve D, 3 poles. Breaking capacity 20 kA at 240 V AC and 10 kA at 415 V AC per EN/IEC 60947-2. Control voltage options include 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC."},{"question":"What is the physical size and mounting?","answer":"Width 99 mm, height 84 mm, depth 77 mm. Mounts on 35 mm symmetrical DIN rail. IP20 rated for enclosed panel use."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C63310","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C63310 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}