{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C64410","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C64410","canonicalUrl":"https://aoctrl.com/schneider/A9C64410","factsUrl":"https://aoctrl.com/api/mcp/products/A9C64410","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60H, integrated control circuit breaker, 10 A, 4P, curve B, 30 kA breaking capacity, 230 V AC control.","salesMarkdown":"It combines overcurrent protection (thermal-magnetic trip, curve B) with local and remote switching capability in a single 4-pole unit rated 10 A. The 30 kA breaking capacity at 230 V AC (15 kA at 380–415 V) per EN/IEC 60947-2 tells you it can safely interrupt fault currents up to that level without upstream damage, which drives selectivity coordination in a distribution board. The fixed mounting and 4-pole width (13 x 9 mm pitches, 117 mm wide) mean it occupies a defined slot in a distribution board; plan the DIN rail fill factor accordingly. ## Control and signalling Control options include a local ON/OFF button, remote pulse, remote continuous command, and toggle — all selectable via the control signal type (maintained very low voltage, maintained, or impulse). The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC, so it integrates with both AC and DC control systems. Local signalling uses a flashing LED for tripped, overheat, or device-ready status, plus a green LED for ON and a red LED for fault — useful for quick panel diagnostics without a meter. A contact position indicator and padlock provision (OFF position) support lockout/tagout procedures.","metaTitle":"Schneider Electric A9C64410 Reflex iC60H, 10 A, 4P, Curve B,","metaDescription":"Schneider Electric A9C64410 Reflex iC60H integrated control MCB. 10 A, 4P, curve B, 30 kA breaking capacity at 230 V. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"77 mm","Range":"Acti9","Width":"117 mm","title":"A9C64410","Colour":"White","Height":"84 mm","Curve code":"B","description":"Reflex iC60H Ti24 10 A 4P curve B integrated control MCB","9 Mm Pitches":"13","Control type":"ON/OFF button Remote control by pulse Remote control by continuous command Toggle","Network type":"AC","Product name":"Reflex iC60","Mounting mode":"Fixed","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"Flashing LED: device tripped Red LED: fault Flashing LED: device overheat Flashing LED: device ready Green LED: device ON","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3","Breaking capacity":"30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"Reflex iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"93 % at 40 °C","Device application":"Distribution Control","[In] rated current":"10 A","Control signal type":"Maintained very low voltage Maintained Impulse","Trip unit technology":"Thermal-magnetic","Electrical durability":"AC-1: 50000 cycles AC 50 Hz","Mechanical durability":"50000 cycles","Breaking capacity code":"H","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"4","Product or component type":"Integrated control circuit breaker","[Us] rated supply voltage":"230 V AC at 50/60 Hz","Contact position indicator":"Yes","Locking options description":"Padlock in OFF position","[Uc] control circuit voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","[Ui] rated insulation voltage":"500 V AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/mk/en/product/download-pdf/A9C64410?filename=Schneider+Electric_EcoStruxure-I-O-Smart-Link_A9C64410.pdf', 'path_name': 'a7262a6276c591793334bf19fdc8aa57.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/a7262a6276c591793334bf19fdc8aa57.pdf', 'status': 1}","sourceUrl":"https://www.se.com/mk/en/product/A9C64410/reflex-ic60h-ti24-10-a-4p-curve-b-integrated-control-mcb/"},"ai":{"faq":[{"question":"What are the key ratings for the A9C64410?","answer":"Rated current 10 A, 4 poles, curve B, breaking capacity 30 kA at 230 V AC and 15 kA at 380–415 V AC per EN/IEC 60947-2. Control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC."},{"question":"What is the A9C64410's depth?","answer":"The listed depth is 77 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C64410","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C64410 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}