{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C66410","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C66410","canonicalUrl":"https://aoctrl.com/schneider/A9C66410","factsUrl":"https://aoctrl.com/api/mcp/products/A9C66410","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60H, integrated control circuit breaker, 10 A, 4P, curve D, 30 kA breaking capacity.","salesMarkdown":"Breaking capacity is 30 kA Icu at 220–240 V AC and 15 kA Icu at 380–415 V AC, per EN/IEC 60947-2 — that's the fault current it can safely interrupt without welding contacts or venting plasma. For a 10 A device, that's serious headroom; it'll hold coordination downstream of a transformer or in a sub-distribution board where fault levels are high. Four poles protected (4P), so it breaks all lines simultaneously on a fault or remote command. The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC — common voltages for building management or PLC-driven panels. Fixed mounting mode, so it stays put once clipped. Dimensions: 117 mm wide (that's 13 modules of 9 mm pitch), 84 mm tall, 77 mm deep. The width is the main panel-space consideration: at 13 pitch units, it's wider than a standard 4P MCB because of the integrated control electronics and the ON/OFF button with local signalling (green LED for ON, red for fault, flashing for trip or overheat). Padlockable in the OFF position — useful for lockout/tagout without needing a separate hasp. Earth-leakage protection is handled by a separate block (not built in), so if you need RCD functionality, you add an external Vigi module downstream. ## What the durability ratings tell you Mechanical endurance is 50,000 cycles; electrical endurance under AC-1 (resistive load) is also 50,000 cycles at 50 Hz. That's typical for a panel-mounted control breaker — not a daily-switch duty cycle, but fine for occasional remote operation or emergency stop reset. The tropicalisation class 2 means it's treated against humidity and fungal growth for use in warm, damp environments (up to 93% RH at 40 °C).","metaTitle":"Schneider Electric A9C66410 Reflex iC60H, 10 A 4P Curve D MC","metaDescription":"Schneider Electric A9C66410 Reflex iC60H integrated control MCB, 10 A rated current, 4 poles, curve D, 30 kA breaking capacity at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White","Depth":"77 mm","Width":"117 mm","Height":"84 mm","IP Rating":"IP20","Application":"Control Distribution","Coil Voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3","Insulation Voltage Ui":"500 V AC","Electrical Life Cycles":"AC-1: 50000 cycles AC 50 Hz","Mechanical Life Cycles":"50000 cycles","Main Product Or Component Type":"Integrated control circuit breaker"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9C66410/reflex-ic60h-ti24-10-a-4p-curve-d-integrated-control-mcb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9C66410/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C66410","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C66410 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}