{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9C66416","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9C66416","canonicalUrl":"https://aoctrl.com/schneider/A9C66416","factsUrl":"https://aoctrl.com/api/mcp/products/A9C66416","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Reflex iC60H Ti24, integrated control circuit breaker, 16 A, 4P, curve D, 230 V AC control, 30 kA breaking capacity.","salesMarkdown":"The Schneider Electric A9C66416 is a Reflex iC60H integrated control circuit breaker from the Acti9 range — a 4-pole thermal-magnetic MCB with a 16 A rated current and a D trip curve, designed to both protect and remotely control a circuit from a single DIN-rail footprint. Rated breaking capacity hits 30 kA Icu at 220…240 V AC and 15 kA Icu at 380…415 V AC, both per EN/IEC 60947-2, which means it can safely interrupt fault currents up to those levels without welding its contacts or cascading failure upstream. Control voltage options include 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC, so you can match whatever control signal your panel already runs — maintained, maintained very low voltage, or impulse commands. ## Where you'd use it This is an integrated control circuit breaker — it combines overcurrent protection (thermal-magnetic trip) with remote ON/OFF switching in one unit, so it's a natural fit for distribution and control panels where you want to shed a load or reset a circuit from a PLC or pushbutton without adding a separate contactor. The IP20 finger-safe terminals are fine for enclosed panels; the white housing and local LED signalling (green for ON, red for fault, flashing for ready/tripped/overheat) give a clear visual at the cabinet door.","metaTitle":"Schneider Electric A9C66416 Reflex iC60H Ti24 16A 4P Curve D","metaDescription":"Schneider Electric A9C66416 Reflex iC60H integrated control MCB, 16 A, 4P, curve D, 30 kA breaking capacity, 230 V AC control. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"77 mm","Range":"Acti9","Width":"117 mm","title":"A9C66416","Colour":"White","Height":"84 mm","Curve code":"D","description":"Reflex iC60H Ti24 16 A 4P curve D integrated control MCB","9 Mm Pitches":"13","Control type":"Remote control by pulse ON/OFF button Toggle Remote control by continuous command","Network type":"AC","Product name":"Reflex iC60","Mounting mode":"Fixed","Tropicalisation":"2","lifecycle_stage":"current","Local signalling":"Green LED: device ON Red LED: fault Flashing LED: device ready Flashing LED: device tripped Flashing LED: device overheat","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3","Breaking capacity":"30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"Reflex iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"93 % at 40 °C","Device application":"Control Distribution","[In] rated current":"16 A","Control signal type":"Maintained Maintained very low voltage Impulse","Trip unit technology":"Thermal-magnetic","Electrical durability":"AC-1: 50000 cycles AC 50 Hz","Mechanical durability":"50000 cycles","Breaking capacity code":"H","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"4","Product or component type":"Integrated control circuit breaker","[Us] rated supply voltage":"230 V AC at 50/60 Hz","Contact position indicator":"Yes","Locking options description":"Padlock in OFF position","[Uc] control circuit voltage":"230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC","[Ui] rated insulation voltage":"500 V AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/mk/en/product/download-pdf/A9C66416?filename=Schneider+Electric_EcoStruxure-I-O-Smart-Link_A9C66416.pdf', 'path_name': 'e242629639e07588c959e3e251bd102a.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/e242629639e07588c959e3e251bd102a.pdf', 'status': 1}","sourceUrl":"https://www.se.com/mk/en/product/A9C66416/reflex-ic60h-ti24-16-a-4p-curve-d-integrated-control-mcb/"},"ai":{"faq":[{"question":"What are the key ratings for this Reflex iC60H?","answer":"16 A rated current, curve D trip characteristic, 4 poles protected, 30 kA breaking capacity at 230 V AC (15 kA at 415 V AC), control voltages available from 24 V DC up to 230 V AC."},{"question":"What control signal types does it accept?","answer":"It accepts maintained signals (including very low voltage), impulse commands, and toggle remote control — so you can drive it from a latching relay, a momentary pushbutton, or a PLC digital output."},{"question":"Does the A9C66416 include earth-leakage protection?","answer":"No, earth-leakage protection requires a separate block — this is the thermal-magnetic MCB only, not an RCBO. You'd add a Vigi iC60 module downstream if you need ground-fault detection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9C66416","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9C66416 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}