{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D01825","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D01825","canonicalUrl":"https://aoctrl.com/schneider/A9D01825","factsUrl":"https://aoctrl.com/api/mcp/products/A9D01825","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, A9D01825, 25 A rated current, C-curve, 10 mA earth leakage, 1P+N, 10 kA breaking capacity.","salesMarkdown":"It combines a 25 A thermal-magnetic MCB (C-curve, 5–10× In magnetic trip) with an integrated 10 mA earth-leakage sensor, all in a 1P+N form factor that switches the phase and monitors the neutral. The 10 mA earth-leakage threshold is the sensitive end of the RCBO range — it catches leakage currents that a 30 mA device would miss, making it the right choice for circuits where additional shock protection is specified (e.g., socket outlets in bathrooms or construction sites per BS 7671). The limitation class 3 rating means the RCBO limits let-through energy in a fault — reduces stress on downstream wiring and equipment compared to a class 2 device. The RCBO is certified to IEC 61009-1 and IEC 61009-2-2 (the product standard for RCBOs), plus the UK variant BS EN 61009-1. The tropicalisation class 2 means the device is treated for operation in warm, humid environments (95% RH at 55 °C). The upstream neutral is plug-on. Strip length is 14 mm for top connection, 13 mm for bottom. These matter when you are wiring a dense board — the 18 mm width leaves limited finger space, so pre-form the conductors.","metaTitle":"Schneider Electric A9D01825 Acti9 iC60 RCBO, 25A C-Curve, 10","metaDescription":"Schneider Electric A9D01825 Acti9 iC60 RCBO, 25A rated current, 10kA breaking capacity, 10mA earth leakage, C-curve, 1P+N. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-2-2 BS EN 61009-1 IEC 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Plug-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication Fault indication","Mounting support":"Isobar A Isobar B","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IEC 61009-2-2","Device short name":"iC60H RCBO PoN","Network frequency":"50/60 Hz","Poles description":"1P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top 2 N.m bottom","[In] rated current":"25 A at 50 °C","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top connection 13 mm for bottom connection","Connections - terminals":"Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...10 mm² flexible Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (bottom) 1...16 mm² rigid Plug-on neutral (upstream)","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"10 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Electrical insulation class":"Class II","Locking options description":"Padlock in on or off position","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz conforming to IEC 61009-2-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$210.93","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/A9D01825/acti9-ic60h-rcbo-plug-on-neutral-1p+ns-25a-c-10000a-10ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D01825/alternatives.json"},"ai":{"faq":[{"question":"What is A9D01825's breaking capacity?","answer":"The A9D01825 has a breaking capacity of 10,000 A Icn at 240 V AC, 50/60 Hz, conforming to IEC 61009-2-2."},{"question":"What earth-leakage sensitivity does this RCBO have?","answer":"The integrated earth-leakage protection is set at 10 mA sensitivity."},{"question":"What is the closest alternative to A9D01825 in the Acti9 range?","answer":"The A9D01825 is the 25 A, 10 mA, C-curve variant in the iC60H RCBO PoN family. The same physical footprint and breaking capacity is available in other current ratings (e.g., 16 A, 32 A) and sensitivities (30 mA, 300 mA) — the choice depends on the subcircuit load and required leakage threshold."},{"question":"Where can I buy A9D01825 and how is it quoted?","answer":"The A9D01825 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D01825","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D01825 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}