{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D02840","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D02840","canonicalUrl":"https://aoctrl.com/schneider/A9D02840","factsUrl":"https://aoctrl.com/api/mcp/products/A9D02840","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H RCBO, 1P + Ns, 40 A, 30 mA, Curve C, 10 kA Icn at 240 V AC, DIN-rail clip-on.","salesMarkdown":"It protects a single-phase outgoer (1P + Ns, neutral left) against overload, short-circuit, and earth leakage in one unit, saving a DIN-rail position compared to separate MCB + RCCB. Rated 40 A at 50 °C with a C curve, 30 mA earth-leakage sensitivity. Compliant with IEC 61009-1 and IEC 61009-2-2. Breaking capacity is 10 kA Icn at 240 V AC 50/60 Hz, limitation class 3, meaning it limits let-through energy enough for most final-distribution panels with a downstream fault. The thermal-magnetic trip unit is sealed — no field adjustment. The modular enclosure carries IP20 (IP40 in the enclosure) — suitable for dry indoor panels. Padlockable with a Ø 4 mm padlock for lockout/tagout. Screw-clamp terminals: top accepts 1…25 mm² rigid or 1…16 mm² flexible; bottom accepts 1…16 mm² rigid or 1…10 mm² flexible. Tightening torque 3.5 N.m top, 2 N.m bottom. Strip length 14 mm top, 13 mm bottom.","metaTitle":"A9D02840 Acti9 iC60H RCBO, 40 A, 30 mA, Curve C, 10 kA","metaDescription":"A9D02840 Acti9 iC60H RCBO, 40 A rated current, 30 mA earth-leakage sensitivity, Curve C, 10 kA breaking capacity at 240 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-1 IEC 61009-2-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"40 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20 IP40 (modular enclosure)","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/hk/en/product/A9D02840/acti9-ic60h-rcbo-1p+ns-c-curve-40-a-30-ma-10000-a-240-v-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D02840/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for A9D02840?","answer":"The A9D02840 is certified to IEC 61009-1 and IEC 61009-2-2. It carries the Acti9 brand's standard compliance documentation for RoHS, REACH, and CE marking; specific declarations are available on request."},{"question":"What is A9D02840's listed depth?","answer":"The A9D02840 has a depth of 77.5 mm, which fits standard DIN-rail enclosures with adequate wiring space."},{"question":"What is A9D02840's listed range?","answer":"The A9D02840 belongs to the Acti9 range, Schneider Electric's modular protection and control platform for final-distribution panels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D02840","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D02840 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}