{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D04845","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D04845","canonicalUrl":"https://aoctrl.com/schneider/A9D04845","factsUrl":"https://aoctrl.com/api/mcp/products/A9D04845","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H RCBO, 1P+N, 45 A, 10 kA Icn, 30 mA earth leakage, Curve B, DIN rail clip-on.","salesMarkdown":"The 30 mA earth-leakage sensitivity catches ground faults that could otherwise go unnoticed until someone gets a shock. The 10 kA Icn at 240 V AC is the rated short-circuit capacity — the maximum fault current the RCBO can safely interrupt. In a domestic or light commercial panel fed by a transformer with a known prospective fault level below 10 kA, this part clears the fault without needing a current-limiting upstream breaker. The 45 A rating at 50 °C means you size it for a continuous load of roughly 36 A (80 % rule for continuous loads per NEC, though local codes vary) — good for a 40 A or 45 A subfeed. Clip-on DIN rail mounting, 2 modules wide (18 mm per module). Strip length is 14 mm for the top, 13 mm for the bottom. The toggle gives clear ON/OFF indication, and the unit is padlockable with a 4 mm padlock for lockout/tagout.","metaTitle":"Schneider Electric A9D04845 Acti9 iC60H RCBO, 45A, 10kA, 30m","metaDescription":"Schneider Electric A9D04845 Acti9 iC60H RCBO, 1P+N, 45A, 10kA breaking capacity, 30mA earth leakage, Curve B, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-1 IEC 61009-2-2","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"45 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20 IP40 (modular enclosure)","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/hk/en/product/A9D04845/acti9-ic60h-rcbo-1p+ns-b-curve-45-a-30-ma-10000-a-240-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D04845/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9D04845?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution."},{"question":"What is A9D04845's listed depth?","answer":"The depth is 77.5 mm."},{"question":"What is A9D04845's listed range?","answer":"It belongs to the Acti9 range, specifically the Acti9 iC60 series."},{"question":"What compliance documentation does this brand provide for A9D04845?","answer":"The part is certified to IEC 61009-1 and IEC 61009-2-2. RoHS and REACH compliance documentation is available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D04845","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D04845 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}