{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D07220","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D07220","canonicalUrl":"https://aoctrl.com/schneider/A9D07220","factsUrl":"https://aoctrl.com/api/mcp/products/A9D07220","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, A9D07220, 2P, 20 A rated, 30 mA earth-leakage sensitivity, C-curve, 10 kA Icn breaking capacity, DIN rail clip-on, white.","salesMarkdown":"## What this RCBO does and why the ratings matter Rated 20 A (C-curve, thermal-magnetic trip) with 30 mA residual-current sensitivity, it handles both overload/short-circuit protection and personnel/equipment ground-fault protection in a single DIN-rail module. The 30 mA sensitivity is the standard threshold for personal shock protection in wet or socket-outlet circuits per IEC 60364. ## Breaking capacity and limitation class Rated breaking capacity is 10 kA Icn at 220–240 V AC 50 Hz per EN/IEC 61009-2-1, with an ultimate breaking capacity (Icu) of 15 kA per EN/IEC 60947-2. This is the difference between a breaker that merely trips and one that limits damage to the load side. Clip-on mounting to standard DIN rail (per IEC/EN 60715). Tunnel terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible (with ferrule) for top or bottom connection; strip length 12 mm, tighten to 2 N·m. IP40 in a distribution enclosure, IP20 on the terminals. The toggle provides local signalling: ON, OFF, and fault-trip indication.","metaTitle":"A9D07220 Acti9 iC60 RCBO, 20 A, 30 mA, C-curve, 2P","metaDescription":"Schneider Electric A9D07220 Acti9 iC60 RCBO, 20 A rated, 30 mA earth leakage, C-curve, 2-pole, 10 kA Icn, DIN rail mount. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Quality labels":"NF KEMA-KEUR VDE IMQ","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 15 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"20 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"2","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA 50 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9D07220/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-2p-20a-c-curve-10000a-15ka-ac-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D07220/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9D07220?","answer":"10 kA Icn at 220–240 V AC 50 Hz per EN/IEC 61009-2-1, with an Icu of 15 kA per EN/IEC 60947-2."},{"question":"What earth-leakage sensitivity does A9D07220 have?","answer":"30 mA sensitivity, integrated into the RCBO, protecting both poles."},{"question":"Where can I buy A9D07220?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D07220","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D07220 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}