{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D10845","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D10845","canonicalUrl":"https://aoctrl.com/schneider/A9D10845","factsUrl":"https://aoctrl.com/api/mcp/products/A9D10845","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H RCBO, 1P+N, 45 A at 50 °C, 10 mA earth-leakage sensitivity, curve C, 10 kA breaking capacity, clip-on DIN rail, IP20.","salesMarkdown":"The Schneider Electric A9D10845 is an Acti9 iC60H RCBO — a residual current breaker with overcurrent protection, combining a 45 A thermal-magnetic MCB (curve C) and a 10 mA earth-leakage detector in a single 18 mm wide module that clips onto a DIN rail. Rated 45 A at 50 °C, it handles the load current for a final subcircuit while the 10 mA sensitivity catches leakage to ground — the kind of spec you see on circuits supplying wet areas or equipment where personnel protection matters. Clip-on mounting on a DIN rail, 18 mm wide (2 x 9 mm pitches), neutral on the left, with screw-clamp terminals accepting up to 25 mm² rigid on the top and 16 mm² on the bottom. Torque settings: 3.5 N.m on the top (line) connection, 2 N.m on the bottom (load). Strip length 14 mm top, 13 mm bottom.","metaTitle":"Schneider Electric A9D10845 Acti9 iC60H RCBO, 45 A, 10 mA, C","metaDescription":"Schneider Electric A9D10845 Acti9 iC60H RCBO, 1P+N, 45 A at 50 °C, 10 mA earth-leakage, 10 kA breaking capacity, curve C. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-2-2 IEC 61009-1 BS EN 61009-1 AS/NZS 61009.1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 230/240 V AC 50/60 Hz","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + Ns","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"45 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"10 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 230/240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/A9D10845/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60h-rcbo-1p+ns-45a-10ma-a-type-10000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D10845/alternatives.json"},"ai":{"faq":[{"question":"What is A9D10845's listed depth?","answer":"The A9D10845 has a depth of 77.5 mm."},{"question":"What is A9D10845's listed range?","answer":"The A9D10845 belongs to the Acti9 range."},{"question":"What compliance documentation does this brand provide for A9D10845?","answer":"The A9D10845 is certified to IEC 61009-2-2, IEC 61009-1, BS EN 61009-1, and AS/NZS 61009.1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D10845","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D10845 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}