{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D14832","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D14832","canonicalUrl":"https://aoctrl.com/schneider/A9D14832","factsUrl":"https://aoctrl.com/api/mcp/products/A9D14832","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H RCBO, 1P+N, 32 A, 30 mA, C-curve, 10 kA, clip-on DIN rail, white.","salesMarkdown":"## What this RCBO does and why the ratings matter It's rated at 32 A (at 50 °C) with a 30 mA earth-leakage sensitivity, C-curve trip characteristic, and a 10 kA breaking capacity (Icn at 240 V AC, per IEC 61009-1). That 30 mA sensitivity is the standard for personal protection against electric shock in TN earthing systems — it catches leakage currents that could be dangerous through a person, while the C-curve handles moderate inrush from motor or lighting loads without nuisance tripping. The limitation class 3 rating (energy let-through) means it limits the fault energy passed downstream, which helps with selective coordination in a panel. Clip-on mounting onto a 45 mm grid DIN rail — standard for Acti9 enclosures. Neutral is on the left, which matters when you're laying out busbars or pre-wired assemblies.","metaTitle":"Schneider Electric A9D14832 Acti9 iC60 RCBO, 32 A, 30 mA, C-","metaDescription":"Schneider Electric A9D14832 Acti9 iC60H RCBO — 32 A rated current, 30 mA earth-leakage sensitivity, C-curve, 10 kA breaking capacity. Active production. Sourced to order against RF","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-1 IEC 61009-2-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IEC 61009-1","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"32 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9D14832/ic60h-earth-leakage-circuit-breaker-1p-+-n-c-curve-32-a-30-ma-240-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D14832/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D14832 and how do I get a price?","answer":"The A9D14832 is available to order through independent distribution. Submit an RFQ to get current pricing and availability confirmed at quote time."},{"question":"What is A9D14832's listed depth (77.5 mm) on this component line?","answer":"The A9D14832 has a depth of 77.5 mm, which is standard for the Acti9 iC60H RCBO range."},{"question":"What compliance documentation does this brand provide for A9D14832?","answer":"The A9D14832 is certified to IEC 61009-1 and IEC 61009-2-2. It carries IP20 and IP40 (modular enclosure) ratings per IEC 60529. For RoHS, REACH, or UL documentation, request the manufacturer's compliance declarations at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D14832","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D14832 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}