{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D14845","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D14845","canonicalUrl":"https://aoctrl.com/schneider/A9D14845","factsUrl":"https://aoctrl.com/api/mcp/products/A9D14845","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, A9D14845, 1P+N, 45 A at 50 °C, 30 mA earth leakage, Type C curve, 10 kA breaking capacity, clip-on DIN rail.","salesMarkdown":"It protects a single-phase outgoing circuit (1P+N) against overload, short-circuit, and earth leakage, all in one DIN-rail footprint. Rated 45 A at 50 °C with a 30 mA earth-leakage sensitivity and a Type C tripping curve, it's the sort of part that keeps a panel builder from having to stack a separate RCD and MCB on the same rail. If your panel runs hotter, you'll need to derate. The integrated 30 mA earth-leakage protection provides personnel protection per IEC 61009-1, catching ground faults before they become a shock hazard. Clip-on mounting to a 45 mm grid DIN rail. IP20 finger-safe protection means it's intended for enclosed panels, not washdown environments. The toggle switch gives local ON/OFF indication, and it's padlockable with a 4 mm hasp for lockout/tagout.","metaTitle":"Schneider Electric A9D14845 Acti9 iC60 RCBO, 45 A, 30 mA, Ty","metaDescription":"Schneider Electric A9D14845 Acti9 iC60 RCBO, 45 A rated current, 30 mA earth leakage, 10 kA breaking capacity, Type C curve. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-2-2 IEC 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"45 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9D14845/ic60h-earth-leakage-circuit-breaker-1p-+-n-c-curve-45-a-30-ma-240-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D14845/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9D14845 and get a price?","answer":"The A9D14845 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the closest alternative to the A9D14845 in the Acti9 range?","answer":"Within the Acti9 iC60 RCBO family, the closest alternative would be a unit with the same 1P+N configuration, Type C curve, and 30 mA sensitivity but a different current rating — for example, a 40 A or 50 A variant. The mechanical footprint (18 mm, clip-on DIN rail) and terminal specifications are identical across the range, so swapping current ratings requires no panel rework."},{"question":"What is the A9D14845's depth?","answer":"The A9D14845 has a depth of 77.5 mm. This is the dimension from the DIN-rail mounting surface to the front of the toggle — relevant for enclosure depth planning."},{"question":"What compliance documentation does Schneider provide for the A9D14845?","answer":"The A9D14845 is certified to IEC 61009-1 and IEC 61009-2-2, the international standards for residual current operated circuit breakers with integral overcurrent protection. Standard Schneider documentation includes the declaration of conformity, which covers CE marking. RoHS and REACH compliance declarations are typically available through Schneider's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D14845","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D14845 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}