{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D15825","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D15825","canonicalUrl":"https://aoctrl.com/schneider/A9D15825","factsUrl":"https://aoctrl.com/api/mcp/products/A9D15825","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H RCBO, A9D15825, 1P+N, 25 A rated, C-curve, 10 kA breaking capacity at 240 V AC, 100 mA earth-leakage sensitivity, thermal-magnetic trip, DIN-rail clip-on.","salesMarkdown":"The Schneider Electric A9D15825 is a 1P+N Acti9 iC60H RCBO — a residual current breaker with overcurrent protection that combines a 25 A thermal-magnetic MCB (C-curve) and a 100 mA earth-leakage module in a single 18 mm wide DIN-rail unit. Rated Icn of 10,000 A at 240 V AC, 50/60 Hz, it clears fault currents up to that level without external fusing — limitation class 3 means it lets through less energy than a standard breaker, which helps downstream selectivity in a distribution board. The integrated earth-leakage protection (100 mA sensitivity) covers personnel and equipment against ground faults on TN earthing systems, and the device is marked suitable for isolation per IEC 61009-1 and IEC 61009-2-2. Depth of 77.5 mm and height of 110 mm fit within a standard distribution board enclosure; the toggle actuator and ON/OFF indicator remain visible after panel wiring. Tightening torque: 3.5 N·m top, 2 N·m bottom. Wire stripping length 14 mm top, 13 mm bottom — these values govern gland-plate planning and torque-driver setup. IP20 finger protection; padlockable with a Ø 4 mm padlock for lockout/tagout. 25 A rated current at 50 °C ambient — the thermal-magnetic trip element is calibrated for that temperature; derate per the manufacturer's curve if installed in a higher ambient (e.g., a sealed enclosure). Limitation class 3 (energy let-through ≤ 15% of a class 1 breaker at the same rating) reduces arc-flash energy and improves coordination with downstream MCBs. Electrical durability of 5,000 cycles and mechanical durability of 20,000 cycles — the electrical figure governs switching under load; the mechanical figure covers routine on/off for isolation. For a final-circuit RCBO switched infrequently, both exceed typical service life.","metaTitle":"Schneider Electric A9D15825 Acti9 iC60 RCBO, 25 A, C-Curve,","metaDescription":"Schneider Electric A9D15825 Acti9 iC60H RCBO, 25 A rated, C-curve, 10 kA breaking capacity at 240 V AC. 1P+N, 100 mA earth-leakage, DIN-rail mount. IEC 61009-1. Current-production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-1 IEC 61009-2-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"25 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9D15825/ic60h-earth-leakage-circuit-breaker-1p-+-n-c-curve-25-a-100-ma-240-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D15825/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Schneider Electric provide for A9D15825?","answer":"The A9D15825 is certified to IEC 61009-1 and IEC 61009-2-2. The manufacturer provides a Declaration of Conformity, datasheet, and installation instructions. RoHS and REACH compliance statements are available on request. No UL or CSA listing is evidenced for this specific order code."},{"question":"What is A9D15825's depth?","answer":"The A9D15825 has a depth of 77.5 mm from the DIN-rail mounting surface to the front of the toggle. This dimension governs enclosure depth selection — allow clearance for wiring and the padlock hasp."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D15825","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D15825 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}