{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D16845","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D16845","canonicalUrl":"https://aoctrl.com/schneider/A9D16845","factsUrl":"https://aoctrl.com/api/mcp/products/A9D16845","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 IKQE RCBO, 1P+N, 45 A, C-curve, 10 kA Icn at 230 V AC, 30 mA earth-leakage sensitivity, clip-on DIN rail mount.","salesMarkdown":"The A9D16845: The 45 A rating at 50 °C is the continuous current the RCBO can carry without tripping under normal load. The C-curve means the magnetic trip operates at 5 to 10 times In (225–450 A), suited for inductive loads like motor starters or fluorescent lighting banks where inrush exceeds a B-curve's threshold. The 30 mA earth-leakage sensitivity provides personal protection against direct contact with live parts, required in circuits supplying socket outlets or portable equipment. The 1P+N configuration switches the line conductor only; the neutral is switched internally for isolation but not protected against overcurrent. The 18 mm width (2 x 9 mm pitches) means this RCBO occupies a single module position on the DIN rail — a tight fit for high-density boards. The A9D16845 is listed as current production with no end-of-life notification. No official successor part exists because it remains the active SKU in the Acti9 range.","metaTitle":"Schneider Electric A9D16845 Acti9 IKQE RCBO, 45A C-Curve 10k","metaDescription":"Schneider Electric A9D16845 Acti9 IKQE RCBO, 45A rated current, C-curve, 10kA breaking capacity at 230V AC, 30mA earth leakage protection, current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"82 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"118 mm","Standards":"BS EN 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"IKQE RCBO","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m top or bottom","[In] rated current":"45 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"10 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"10000 A at 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/A9D16845/ikqe-earth-leakage-circuit-breaker-1p-+-n-c-curve-45-a-10-ma-230-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D16845/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D16845","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D16845 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}