{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D17225","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D17225","canonicalUrl":"https://aoctrl.com/schneider/A9D17225","factsUrl":"https://aoctrl.com/api/mcp/products/A9D17225","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, A9D17225, 2P, 25 A rated current, C-curve, 30 mA earth-leakage sensitivity, 10 kA Icn breaking capacity, clip-on DIN rail mount.","salesMarkdown":"## Panel-builder note: A9D17225 Acti9 iC60 RCBO The Schneider Electric A9D17225 is an Acti9 iC60 RCBO — a combined miniature circuit breaker and residual-current device in a single 36 mm wide, 2-pole module. Clip-on mounting to the DIN rail and tunnel terminals accepting up to 35 mm² rigid conductors make for straightforward panel integration. The 25 A rating and C-curve suit it for general-purpose branch circuit protection in distribution boards — motor circuits, lighting, socket outlets. The 30 mA earth-leakage threshold provides personal protection against direct contact. Breaking capacity is 10 kA Icn per EN/IEC 61009-2-1 at 220-240 V AC, 50 Hz, with an ultimate breaking capacity (Icu) of 15 kA per EN/IEC 60947-2. Toggle control with local signalling for ON, OFF, and fault trip. Wire stripping length 12 mm for top or bottom connection; tunnel terminals accept 1-35 mm² rigid or 1-25 mm² flexible. Tightening torque 2 N.m. IP40 in distribution enclosure, IP20 otherwise. Overvoltage category III per IEC 60364. Tropicalisation class 2. Rated for 10,000 electrical and 20,000 mechanical cycles. Humidity tolerance 95% at 55 °C.","metaTitle":"Schneider Electric A9D17225 Acti9 iC60 RCBO, 25 A, C-curve,","metaDescription":"Schneider Electric A9D17225 Acti9 iC60 RCBO, 25 A rated current, C-curve, 30 mA earth-leakage sensitivity, 10 kA Icn. Sourced to order against RFQ. EN/IEC 60947-2 & 61009-2-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Quality labels":"NF KEMA-KEUR IMQ VDE","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 15 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"2","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA 50 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9D17225/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-2p-25a-c-curve-10000a-15ka-a-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D17225/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D17225 and get current pricing?","answer":"The A9D17225 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of A9D17225?","answer":"The A9D17225 has a rated short-circuit capacity (Icn) of 10,000 A at 220-240 V AC, 50 Hz per EN/IEC 61009-2-1, and an ultimate breaking capacity (Icu) of 15 kA at the same voltage per EN/IEC 60947-2."},{"question":"What compliance standards does A9D17225 meet?","answer":"The A9D17225 is certified to EN/IEC 60947-2 and EN/IEC 61009-2-1, carries quality labels NF, KEMA-KEUR, IMQ, VDE, and is rated overvoltage category III per IEC 60364."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D17225","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D17225 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}