{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D17313","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D17313","canonicalUrl":"https://aoctrl.com/schneider/A9D17313","factsUrl":"https://aoctrl.com/api/mcp/products/A9D17313","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 3P, 13 A, C-curve, 30 mA earth-leakage, 10 kA Icn, DIN rail clip-on.","salesMarkdown":"The A9D17313 is a 3-pole RCBO from the Acti9 iC60 range, combining thermal-magnetic overcurrent protection (13 A rated, C-curve) with integrated 30 mA earth-leakage protection in a single DIN-rail module. It clips onto the rail and occupies 6 x 9 mm pitches (54 mm wide), fitting standard distribution boards. The breaking capacity is 10 kA Icn per EN/IEC 61009-2-1 at 220–240 V AC, 50 Hz, with an ultimate breaking capacity (Icu) of 15 kA per EN/IEC 60947-2. The 30 mA earth-leakage sensitivity provides personal protection against indirect contact (touch voltage) per IEC 60364. The IP40 face (in enclosure) and IP20 terminals suit clean, dry panel environments; not rated for washdown. Local signalling (ON, OFF, fault trip) visible through the white toggle. Tropicalisation class 2 for humid environments up to 95 % RH at 55 °C.","metaTitle":"A9D17313 Acti9 iC60 RCBO, 3P, 13 A, C-curve, 30 mA, DIN rail","metaDescription":"Schneider Electric A9D17313 Acti9 iC60 RCBO, 3-pole, 13 A rated, C-curve, 30 mA earth leakage, 10 kA Icn, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Quality labels":"IMQ NF KEMA-KEUR VDE","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"1 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 15 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA 50 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9D17313/acti9-ic60-rcbo-3p-13-a-c-curve-10000a-15ka-30-ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D17313/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D17313?","answer":"The A9D17313 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is A9D17313's earth-leakage sensitivity?","answer":"The integrated earth-leakage protection is set at 30 mA sensitivity, providing personal protection against indirect contact."},{"question":"What is the breaking capacity of A9D17313?","answer":"The breaking capacity is 10 kA Icn at 220–240 V AC 50 Hz per EN/IEC 61009-2-1, with an ultimate breaking capacity (Icu) of 15 kA per EN/IEC 60947-2."},{"question":"What compliance documentation does Schneider provide for A9D17313?","answer":"The A9D17313 carries quality labels IMQ, NF, KEMA-KEUR, and VDE, and complies with EN/IEC 60947-2 and EN/IEC 61009-2-1 standards. RoHS/REACH/UL documentation is typically provided by the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D17313","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D17313 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}