{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D17825","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D17825","canonicalUrl":"https://aoctrl.com/schneider/A9D17825","factsUrl":"https://aoctrl.com/api/mcp/products/A9D17825","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 IKQE RCBO, 1P+N, 25 A, 30 mA, 10 kA, C-curve, thermal-magnetic, DIN rail mount.","salesMarkdown":"It protects a single-pole-plus-neutral outgoing circuit against both overload/short-circuit (thermal-magnetic trip, C-curve) and earth leakage (30 mA sensitivity). Clip it onto a DIN rail, torque the tunnel terminals to 2 N·m, and it's ready for a 50 Hz network. The 25 A rated current at 50 °C is the continuous load the RCBO can carry without tripping — size it for the circuit's full-load current, not the breaker's maximum. The 30 mA earth-leakage sensitivity is the standard for personal protection against indirect contact; it will trip on a fault current above that threshold. The 18 mm width takes two 9 mm pitches on a DIN rail, leaving room for adjacent modules in a distribution board. It is padlockable with a 4 mm padlock for lockout/tagout. The ON/OFF indicator and contact position indicator give visual confirmation of state. Compliance to BS EN 61009-1 covers the UK and many Commonwealth markets for RCBOs.","metaTitle":"Schneider Electric A9D17825 Acti9 IKQE RCBO, 25 A, 30 mA, 10","metaDescription":"Schneider Electric A9D17825 Acti9 IKQE RCBO, 25 A rated current, 30 mA earth leakage, 10 kA breaking capacity. BS EN 61009-1. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"82 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"118 mm","Standards":"BS EN 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"IKQE RCBO","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m top or bottom","[In] rated current":"25 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"10000 A at 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/A9D17825/ikqe-earth-leakage-circuit-breaker-1p-+-n-c-curve-25-a-30-ma-230-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D17825/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D17825 and what is the lead time?","answer":"The A9D17825 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to A9D17825 in the Acti9 family?","answer":"Within the Acti9 IKQE range, the key variant difference is the rated current — the A9D17825 is the 25 A C-curve 30 mA version. Other current ratings (e.g. 16 A, 32 A) share the same 18 mm footprint, 10 kA breaking capacity, and BS EN 61009-1 compliance, so the choice is purely by circuit load."},{"question":"What compliance documentation does A9D17825 carry?","answer":"The A9D17825 is certified to BS EN 61009-1, the harmonized standard for RCBOs. It is designed for TN earthing systems and 50 Hz networks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D17825","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D17825 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}