{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D18806","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D18806","canonicalUrl":"https://aoctrl.com/schneider/A9D18806","factsUrl":"https://aoctrl.com/api/mcp/products/A9D18806","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 IKQE RCBO, 1P+N, 6 A, C-curve, 10 kA Icn, 100 mA earth-leakage, thermal-magnetic, clip-on DIN rail.","salesMarkdown":"It is rated 6 A at 50 °C with a C-curve trip characteristic and a 10 000 A Icn breaking capacity at 230 V AC, 50/60 Hz. The integrated earth-leakage protection is set to 100 mA sensitivity, covering both overcurrent and ground-fault in one DIN-rail clip-on unit. The 6 A rated current at 50 °C is the continuous load the RCBO can carry without tripping; for a distribution board in a warm cabinet, that derating is already baked in — no extra headroom needed for ambient temperature up to 50 °C. For a typical TN earthing system with a 6 A outgoing circuit, 10 kA is well above the prospective fault level at the board end of most commercial runs. The module occupies 2 x 9 mm pitches — 18 mm wide. Neutral is on the left. Tunnel-type terminals accept 1…16 mm² rigid or 1…10 mm² flexible conductors; tighten to 2 N·m. Strip 13 mm. The toggle control gives local ON/OFF indication. Padlockable with a Ø 4 mm padlock. Designed and tested to BS EN 61009-1, the harmonized standard for RCBOs. The part is suitable for isolation and has a contact position indicator. The electrical durability is rated at 5000 cycles, mechanical at 20 000 cycles. Limitation class 3 indicates good energy-limiting performance under short-circuit conditions.","metaTitle":"Schneider Electric A9D18806 IKQE RCBO, 6A C-curve 10kA 100mA","metaDescription":"Schneider Electric A9D18806 IKQE RCBO, 6A rated, C-curve, 10kA breaking capacity, 100mA earth leakage. BS EN 61009-1. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"82 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"118 mm","Standards":"BS EN 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"IKQE RCBO","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m top or bottom","[In] rated current":"6 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"10000 A at 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/A9D18806/ikqe-earth-leakage-circuit-breaker-1p-+-n-c-curve-6-a-100-ma-230-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D18806/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D18806 and what is the lead time?","answer":"The A9D18806 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest position."},{"question":"What is A9D18806's breaking capacity?","answer":"The A9D18806 has a breaking capacity of 10 000 A Icn at 230 V AC, 50/60 Hz."},{"question":"What standards does A9D18806 comply with?","answer":"The A9D18806 is designed to BS EN 61009-1, the harmonized standard for residual current breakers with overcurrent protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D18806","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D18806 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}