{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D18810","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D18810","canonicalUrl":"https://aoctrl.com/schneider/A9D18810","factsUrl":"https://aoctrl.com/api/mcp/products/A9D18810","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 IKQE RCBO, 1P+N, 10 A rated current, 100 mA earth-leakage sensitivity, C-curve, 10 kA Icn at 230 V AC, 2-module wide (18 mm), clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9D18810 is an Acti9 IKQE RCBO — a combined residual current breaker with overcurrent protection, rated 10 A at 50 °C with 100 mA earth-leakage sensitivity and a C-curve trip characteristic. The 10 A rating at 50 °C means this RCBO is sized for a final subcircuit feeding lighting, general-purpose sockets, or small resistive loads — not motor circuits or high-inrush equipment. The 100 mA earth-leakage threshold is for protection against fire risk rather than personal shock — most socket circuits in a TN system would use 30 mA for personnel protection; this is typically specified for feeders, fixed equipment, or circuits where the earth-leakage background is higher. It complies with BS EN 61009-1, the harmonized standard for RCBOs in the UK and EU. The limitation class 3 means it limits let-through energy well — good for cable protection downstream. At 18 mm width (2 modules), it fits the Acti9 modular grid; leave space for a padlock with Ø 4 mm hasp if you need lockout. Tighten to 2 N·m. The IP20 rating means it is for indoor, dry environments only — no washdown or outdoor exposure.","metaTitle":"Schneider Electric A9D18810 Acti9 IKQE RCBO, 10 A, 100 mA, C","metaDescription":"Schneider Electric A9D18810 Acti9 IKQE RCBO. 10 A rated current, 100 mA earth-leakage sensitivity, C-curve, 10 kA breaking capacity. BS EN 61009-1. Current production. Available to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"82 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"118 mm","Standards":"BS EN 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"IKQE RCBO","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m top or bottom","[In] rated current":"10 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"10000 A at 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/A9D18810/ikqe-earth-leakage-circuit-breaker-1p-+-n-c-curve-10-a-100-ma-230-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D18810/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D18810 and how do I get a price?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for a firm price and availability confirmation — pricing and stock levels are confirmed at quote time, not published here."},{"question":"What is A9D18810's rated current and earth-leakage sensitivity?","answer":"Rated current is 10 A at 50 °C, and earth-leakage sensitivity is 100 mA. The trip curve is C."},{"question":"What compliance standards does A9D18810 meet?","answer":"It complies with BS EN 61009-1, the standard for RCBOs in the UK and EU. The breaking capacity is 10 kA Icn at 230 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D18810","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D18810 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}