{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D18832","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D18832","canonicalUrl":"https://aoctrl.com/schneider/A9D18832","factsUrl":"https://aoctrl.com/api/mcp/products/A9D18832","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 IKQE RCBO, 1P+N, 32 A, 10 kA, 100 mA, Curve C, thermal-magnetic, DIN rail, IP20.","salesMarkdown":"It protects a 1P+N circuit at 32 A rated current (50 °C ambient) with a 10 kA breaking capacity at 230 V AC, and adds integrated earth-leakage protection set at 100 mA sensitivity. The 32 A rating at 50 °C means this RCBO carries a full 32 A load continuously at typical panel ambient temperatures without derating — useful for final subcircuits feeding socket outlets or fixed equipment in distribution boards. The 100 mA earth-leakage sensitivity is a deliberate choice — it's less sensitive than the typical 30 mA used for personal protection, so it's better suited for circuits where some natural leakage is expected (long cable runs, multiple IT loads) and the priority is fire protection or equipment protection rather than shock prevention. Thermal-magnetic trip technology means the thermal bimetal handles overloads (slow, inverse-time) and the solenoid handles short-circuits (instantaneous). No electronics to fail, no auxiliary power needed for the trip function. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; tighten to 2 N·m. Rated for TN earthing systems only. The device is intended as an outgoer in the distribution board — not a main switch. It is suitable for isolation (full contact position indicator and padlockable with a Ø4 mm padlock). Electrical durability is 5,000 cycles; mechanical durability 20,000 cycles. For a final-circuit RCBO switched infrequently (once a week or less) that's a long service life; for frequent switching duty (daily on/off) consider a contactor instead.","metaTitle":"Schneider Electric A9D18832 IKQE RCBO, 32 A, 10 kA, 100 mA,","metaDescription":"Schneider Electric A9D18832 Acti9 IKQE RCBO. 32 A rated current, 10 kA breaking capacity, 100 mA earth leakage, Curve C, 1P+N, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"82 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"118 mm","Standards":"BS EN 61009-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"IKQE RCBO","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 2 N.m top or bottom","[In] rated current":"32 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"10000 A at 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ie/en/product/A9D18832/ikqe-earth-leakage-circuit-breaker-1p-+-n-c-curve-32-a-100-ma-230-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D18832/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9D18832 and get a price?","answer":"The A9D18832 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is the A9D18832's breaking capacity?","answer":"10,000 A Icn at 230 V AC, 50/60 Hz — sufficient for most final-distribution fault levels in TN systems."},{"question":"What standard does the A9D18832 comply with?","answer":"It is certified to BS EN 61009-1, the harmonized standard for RCBOs combining overcurrent and residual current protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D18832","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D18832 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}