{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D31716","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D31716","canonicalUrl":"https://aoctrl.com/schneider/A9D31716","factsUrl":"https://aoctrl.com/api/mcp/products/A9D31716","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi RCBO, A9D31716, 3P+N, 16 A, C-curve, 30 mA earth leakage, 6 kA Icn, DIN rail clip-on.","salesMarkdown":"## What ships in the box Rated 16 A with a C-curve magnetic trip (5–10 x In) and integrated 30 mA earth-leakage protection, it breaks fault currents up to 6000 A Icn at 380–415 V AC per EN/IEC 61009-2-1. No separate RCD block to order — the leakage detection is built in. ## Panel fit and fill factor This RCBO occupies 10 x 9 mm pitches (90 mm wide) on the DIN rail, with a depth of 78.5 mm and height of 91 mm. ## Selectivity and coordination Pollution degree 3 (industrial environment, conductive or dry non-conductive pollution). IP20 on the device body, IP40 inside a modular enclosure. Rated for 90 % relative humidity at 55 °C. The standards listing is EN/IEC 61009-2-1 — the harmonized RCBO standard covering overcurrent and residual-current protection.","metaTitle":"Schneider Electric A9D31716 Acti9 DPN Vigi, 16 A C-curve RCB","metaDescription":"Schneider Electric A9D31716 Acti9 DPN Vigi RCBO, 16 A, C-curve, 30 mA earth leakage, 6 kA breaking capacity, EN/IEC 61009-2-1. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"90 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"10","Control type":"Toggle","Network type":"AC","Product name":"Acti9 DPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases 9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 380...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"DPN N Vigi","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"90 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Sealable Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"440 V AC 50/60 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"380...415 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 6000 A at 380...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-30...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 380...415 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$91.54","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/A9D31716/acti9-dpn-n-vigi-rcbo-3p+n-16a-c-curve-6000a-30ma-type-ac/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D31716/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D31716 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at that time."},{"question":"What is A9D31716's listed depth?","answer":"The depth is 78.5 mm — the critical dimension for enclosure clearance on a DIN-rail mounted RCBO."},{"question":"What compliance documentation does this brand provide for A9D31716?","answer":"The part is certified to EN/IEC 61009-2-1, carries pollution degree 3 and tropicalisation class 2 per IEC 60068-1, and is rated overvoltage category III per IEC 60364."},{"question":"What does the 30 mA earth-leakage sensitivity mean for installation?","answer":"30 mA is the standard sensitivity for personal protection against indirect contact in final circuits — it trips before leakage current reaches a hazardous level for a human in contact with an exposed conductive part."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D31716","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D31716 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}