{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D34816","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D34816","canonicalUrl":"https://aoctrl.com/schneider/A9D34816","factsUrl":"https://aoctrl.com/api/mcp/products/A9D34816","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 1P+N, 16 A, 10 kA, 30 mA, curve B, DIN rail.","salesMarkdown":"It protects a single pole plus neutral (1P+N) on TN earthing systems, rated 16 A at 50 °C with a 10 kA breaking capacity (Icn at 240 V AC). The integrated earth-leakage trips at 30 mA sensitivity, covering both overcurrent and ground-fault protection in one DIN-rail unit. The toggle provides ON/OFF indication and the unit is padlockable with a 4 mm shackle for lockout/tagout.","metaTitle":"Schneider Electric A9D34816 Acti9 iC60 RCBO, 16 A, 10 kA, 30","metaDescription":"Schneider Electric A9D34816 Acti9 iC60 RCBO, 1P+N, 16 A, 10 kA breaking capacity, 30 mA earth leakage, curve B. DIN rail mount, current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-2-2 IEC 61009-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"16 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9D34816/ic60h-earth-leakage-circuit-breaker-1p-+-n-b-curve-16-a-30-ma-240-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D34816/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D34816 and how do I get a price?","answer":"The A9D34816 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is A9D34816's listed depth (77.5 mm) on this component line?","answer":"The A9D34816 has a depth of 77.5 mm, which is standard for the Acti9 iC60 RCBO family and fits typical DIN-rail enclosures."},{"question":"What compliance documentation does this brand provide for A9D34816 (RoHS, REACH, UL, IEC)?","answer":"The A9D34816 is certified to IEC 61009-1 and IEC 61009-2-2. For RoHS, REACH, and other regional declarations, the manufacturer provides compliance documentation on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D34816","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D34816 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}