{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D34832","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D34832","canonicalUrl":"https://aoctrl.com/schneider/A9D34832","factsUrl":"https://aoctrl.com/api/mcp/products/A9D34832","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H RCBO, 1P+N, B-curve, 32 A, 10 kA Icn at 240 V AC, 30 mA earth-leakage, DIN-rail clip-on.","salesMarkdown":"The Schneider Electric A9D34832 is an Acti9 iC60H RCBO — a combined residual-current circuit breaker with overcurrent protection in a single 18 mm wide, 1P+N module. It protects a final subcircuit against overload, short-circuit (B-curve, 32 A rated current at 50 °C), and earth leakage (30 mA sensitivity) in TN earthing systems on AC 50 Hz networks. B-curve means the magnetic trip operates at 3 to 5 times In (96 A to 160 A for this 32 A unit) — suited for resistive and general-purpose loads with modest inrush, such as lighting, socket outlets, and small office equipment. A C-curve would be preferred for motor or transformer circuits with higher inrush; specifying B here avoids nuisance tripping on the intended load type. The 30 mA earth-leakage sensitivity meets the standard requirement for additional protection against direct contact in final circuits (IEC 60364-4-41). Integrated earth-leakage protection means this single module replaces both a separate MCB and RCCD, saving one DIN position in the board. Rated 32 A at 50 °C — the thermal-magnetic trip is calibrated at that ambient. In a 40 °C enclosure the continuous current capacity is higher; in a 60 °C environment (e.g., unventilated panel near a heat source) you must derate. The manufacturer's thermal derating curves (not reproduced here) govern the actual ampacity in your specific enclosure fill. Depth of 77.5 mm and height of 110 mm fit within typical distribution board envelopes; verify clearance for the toggle and the padlock hasp when the enclosure door closes. The A9D34832 is designed and certified to IEC 61009-1 and IEC 61009-2-2 — the international standards for RCBOs covering both overcurrent and residual-current protection. It carries suitability for isolation, meaning it can be used as a disconnecting means for the outgoing circuit.","metaTitle":"Schneider Electric A9D34832 Acti9 iC60H RCBO, B-Curve 32 A,","metaDescription":"Schneider Electric A9D34832 Acti9 iC60H RCBO, 1P+N, B-curve 32 A, 10 kA Icn at 240 V AC, 30 mA earth-leakage, DIN-rail mount. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-1 IEC 61009-2-2","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Grid distance":"45 mm","Mounting mode":"Clip-on","Earthing system":"TN","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz","Device short name":"iC60H RCBO","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"32 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ae/en/product/A9D34832/ic60h-earth-leakage-circuit-breaker-1p-+-n-b-curve-32-a-30-ma-240-v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D34832/alternatives.json"},"ai":{"faq":[{"question":"Who supplies A9D34832 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Volume pricing and lead time are confirmed at the time of quotation."},{"question":"What is A9D34832's listed depth (77.5 mm) on this component line?","answer":"The listed depth is 77.5 mm. This dimension, combined with the 18 mm width and 110 mm height, fits standard distribution board envelopes."},{"question":"What is A9D34832's listed range (Acti9) on this component line?","answer":"The A9D34832 belongs to the Schneider Electric Acti9 range, specifically the iC60H RCBO sub-family."},{"question":"What compliance documentation does this brand provide for A9D34832 (RoHS, REACH, UL, IEC)?","answer":"The A9D34832 is designed and certified to IEC 61009-1 and IEC 61009-2-2. For RoHS, REACH, and UL declarations, refer to the manufacturer's product compliance documentation available via the Schneider Electric portal."},{"question":"Where can I buy A9D34832?","answer":"This part is available to order through independent distribution against an RFQ. Submit a request for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D34832","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D34832 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}