{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D35613","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D35613","canonicalUrl":"https://aoctrl.com/schneider/A9D35613","factsUrl":"https://aoctrl.com/api/mcp/products/A9D35613","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 13 A, C-curve, 30 mA earth leakage, 4.5 kA breaking capacity, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9D35613 is an Acti9 iDPN Vigi combined residual-current circuit breaker (RCBO) — one module wide, 1P+N, rated 13 A with a C-curve magnetic trip (5–10 × In) and integrated 30 mA earth-leakage protection. The 4.5 kA Icn breaking capacity at 230–240 V AC, 50 Hz, per EN/IEC 61009-2-1, covers most final-circuit fault levels in those settings. The 30 mA earth-leakage sensitivity provides personal protection against direct-contact faults, required in most residential and commercial final circuits. The thermal-magnetic trip unit handles both overload (thermal bimetal) and short-circuit (solenoid) without external auxiliaries. The 1P+N configuration switches the phase and breaks the neutral, but the neutral pole is not protected against overcurrent — only the phase pole is. That is standard for single-phase RCBOs in this form factor. The neutral sits on the left side of the module, which matters when aligning busbar connections in a multi-way board. Clip-on mounting to DIN rail (EN 60715) — no screws needed. The 36 mm width (4 × 9 mm pitches) matches the standard Acti9 modular grid. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible (with or without ferrule); strip length is 15 mm, tightening torque 2 N·m. That covers most final-circuit cable sizes up to 4 mm² for a 13 A circuit. The toggle indicates ON, OFF, and fault-trip positions, so a quick visual check tells you whether the device tripped on overcurrent or leakage.","metaTitle":"Schneider Electric A9D35613 Acti9 iDPN Vigi RCBO, 13 A, 30 m","metaDescription":"Schneider Electric A9D35613 Acti9 iDPN Vigi RCBO. 13 A rated current, 30 mA earth leakage, C-curve, 4.5 kA breaking capacity, 1P+N, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"4500 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPNa Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 4500 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"4500 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/A9D35613/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-idpna-vigi-1p+n-13a-c-curve-4500a-a-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D35613/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9D35613 and how do I get a price?","answer":"The A9D35613 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is the closest pin-compatible alternative to A9D35613 in this component family?","answer":"Within the Acti9 iDPN Vigi family, the closest alternatives differ by rated current (In) and earth-leakage sensitivity. For example, the A9D35614 is the same RCBO with a 16 A rating instead of 13 A. The physical footprint and wiring are identical."},{"question":"What compliance documentation does this brand provide for A9D35613?","answer":"The A9D35613 is certified to EN/IEC 61009-2-1, which covers the combined overcurrent and residual-current function. It also carries IP20/IP40 ratings per IEC 60529 and tropicalisation class 2 per IEC 60068-1. For RoHS/REACH declarations, refer to the Schneider Electric product compliance portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D35613","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D35613 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}