{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D37213","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D37213","canonicalUrl":"https://aoctrl.com/schneider/A9D37213","factsUrl":"https://aoctrl.com/api/mcp/products/A9D37213","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, 13 A, 30 mA, Curve B, 2P, 10 kA Icn, DIN-rail mount.","salesMarkdown":"Rated 13 A with a B-curve magnetic trip (3 to 5 x In) and 30 mA earth-leakage sensitivity, it fits distribution sub-circuits where both fault types must be cleared in one unit. Breaking capacity is 10 kA Icn at 230 V AC per EN/IEC 61009-2-1, with an ultimate capacity (Icu) of 15 kA at the same voltage per EN/IEC 60947-2. The 10 kA Icn covers the vast majority of commercial and light-industrial panel fault levels; the higher Icu gives margin for coordination studies where the upstream device limits let-through energy. The 30 mA earth-leakage threshold provides additional protection against indirect contact and fire risk from leakage to earth. Integrated into the RCBO package, it eliminates a separate RCD module and saves one DIN module of width — the unit occupies 4 pitches of 9 mm (36 mm total). This is relevant when coordinating with sensitive electronics or long cable runs. Tunnel-type terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible conductors; strip length is 12 mm and tightening torque is 2 N·m. IP40 faceplate rating in a distribution enclosure (IP20 for the terminals) suits indoor panel environments. The white housing with toggle control provides local ON/OFF and fault-trip indication. Rated for 10,000 electrical cycles and 20,000 mechanical cycles — sufficient for typical branch-circuit duty in commercial and light-industrial panels.","metaTitle":"A9D37213 Acti9 iC60 RCBO, 13 A, 30 mA, Curve B, 2P","metaDescription":"Schneider Electric A9D37213 Acti9 iC60 RCBO, 13 A rated, 30 mA earth-leakage, Curve B, 2-pole, 10 kA breaking capacity. Certified to EN/IEC 60947-2 and EN/IEC 61009-2-1. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"78 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"86 mm","Standards":"EN/IEC 60947-2 EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Quality labels":"IMQ NF VDE KEMA-KEUR","Tropicalisation":"2","lifecycle_stage":"current","Connection pitch":"9 mm between poles","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 15 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"iC60 RCBO","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule","IP degree of protection":"IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"2","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"No conforming to IEC 60947-1","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA 50 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES Bottom: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9D37213/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ic60-2p-13a-b-curve-10000a-15ka-a-type-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D37213/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9D37213?","answer":"Icn is 10 kA at 230 V AC per EN/IEC 61009-2-1; Icu is 15 kA at the same voltage per EN/IEC 60947-2."},{"question":"What compliance documentation does Schneider provide for A9D37213?","answer":"The device is certified to EN/IEC 60947-2 and EN/IEC 61009-2-1, with quality marks IMQ, NF, VDE, and KEMA-KEUR. Declaration of conformity and test reports are available from Schneider Electric."},{"question":"Where can I buy A9D37213 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D37213","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D37213 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}