{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D40610","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D40610","canonicalUrl":"https://aoctrl.com/schneider/A9D40610","factsUrl":"https://aoctrl.com/api/mcp/products/A9D40610","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 10 A, C-curve, 30 mA earth leakage, 6 kA breaking capacity, DIN rail mount.","salesMarkdown":"It protects a single phase against overload, short-circuit, and earth leakage from a single DIN-rail footprint. Rated 10 A at 30 °C with a 6 kA breaking capacity (Icn at 230/240 V AC, 50 Hz), it is sized for final subcircuits in residential and commercial distribution boards where both overcurrent and earth-leakage protection are required on the same outgoing way. The 30 mA earth-leakage sensitivity provides additional protection against indirect contact and fire risk from earth faults — standard for socket-outlet circuits and wet-area final subcircuits in most IEC-based installations. The C-curve magnetic trip (5–10 × In) suits loads with moderate inrush, such as lighting banks, small appliances, and general-purpose socket circuits. The 6 kA breaking capacity is the standard domestic/commercial rating under IEC 61009-1; it is adequate for most final subcircuits fed by a transformer or a main switchboard with a prospective fault current below 6 kA. For higher fault levels, a current-limiting upstream MCB or fuse would be needed. Integrated earth-leakage protection means this RCBO replaces two separate devices (MCB + RCCB) in one 18 mm wide module, saving two DIN-rail pitches per way. The thermal-magnetic trip unit provides the overcurrent protection; the residual current coil handles the earth-leakage function. The 18 mm width occupies two 9 mm pitches, matching the Acti9 modular system for clean row alignment. IP20 finger-safe terminals suit installation inside a locked or tool-accessible enclosure. The tunnel-type terminals accept up to 16 mm² rigid upstream and 10 mm² downstream, covering standard 1.5–6 mm² final subcircuit wiring. Strip length is 13 mm upstream, 11 mm downstream.","metaTitle":"Schneider Electric A9D40610 Acti9 RCBO, 10 A, 30 mA, 6 kA","metaDescription":"Schneider Electric A9D40610 Acti9 iDPN Vigi RCBO. 10 A rated, 30 mA earth leakage, 6 kA breaking capacity, C-curve. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"93 mm","Standards":"IEC 61009-2-2 AS/NZS 61009.1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"ISPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"6000 A Icn at 230/240 V AC 50 Hz","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m upstream 2 N.m downstream","[In] rated current":"10 A at 30 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"11 mm for downstream connection 13 mm for upstream connection","Connections - terminals":"Tunnel type terminal (upstream) 1...16 mm² rigid Tunnel type terminal (downstream) 1...10 mm² rigid Tunnel type terminal (upstream) 1...16 mm² flexible Tunnel type terminal (downstream) 1...10 mm² flexible","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"10 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50 Hz","Ambient air temperature for storage":"-25...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-25...55 °C","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 500 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nz/en/product/A9D40610/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-ispn-vigi-1p-+-n-10a-10ma-a-type-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D40610/alternatives.json"},"ai":{"faq":[{"question":"What is the A9D40610 used for?","answer":"The A9D40610 is a 1P+N RCBO that provides combined overcurrent and earth-leakage protection for a single-phase final subcircuit. It is used in residential and commercial distribution boards where both MCB and RCD functions are needed in one 18 mm module."},{"question":"What is the breaking capacity of the A9D40610?","answer":"The A9D40610 has a breaking capacity of 6 kA Icn at 230/240 V AC, 50 Hz, which is the standard rating for domestic and commercial final subcircuits under IEC 61009-1."},{"question":"Where can I buy the A9D40610?","answer":"The A9D40610 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D40610","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D40610 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}