{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D51210","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D51210","canonicalUrl":"https://aoctrl.com/schneider/A9D51210","factsUrl":"https://aoctrl.com/api/mcp/products/A9D51210","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 RCBO, A9D51210, 2P, 10 A rated, C-curve, 300 mA earth leakage, 10 kA breaking capacity, clip-on DIN rail.","salesMarkdown":"It combines thermal-magnetic overcurrent protection (C-curve, 10 A at 50 °C) with integrated earth-leakage protection set at 300 mA sensitivity. The 10 kA breaking capacity (Icn at 240 V AC, per IEC 61009-1) handles fault currents typical of commercial and light industrial outgoing circuits. The 10 A rated current at 50 °C is the continuous load the RCBO can carry without tripping — derate further if ambient exceeds 50 °C. The 300 mA earth-leakage threshold is a protection level for equipment rather than personnel — it catches insulation faults and ground leaks without nuisance-tripping on capacitive leakage from long cable runs or filters. The 2-pole form factor (switching both line and neutral) with neutral on the left is standard for TT, TN, and IT earthing systems, so it drops into most distribution boards without rework. IP20 (finger-safe terminals) and IP40 within a modular enclosure mean it is intended for enclosed distribution boards, not wet or dusty environments. The 77.5 mm depth fits standard consumer unit and panelboard depths — verify door clearance if the board has a shallow cover. Certified to IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1 — the core standards for RCBOs combining overcurrent and residual current protection. Suitable for isolation (marked with the isolation symbol).","metaTitle":"Schneider Electric A9D51210 Acti9 iC60 RCBO, 10A C-curve 2P","metaDescription":"Schneider Electric A9D51210 Acti9 iC60 RCBO, 10A rated current, C-curve, 2-pole, 300mA earth leakage, 10kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"110 mm","Standards":"IEC 61009-2-2 AS/NZS 61009.1 IEC 61009-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60 RCBO","Mounting mode":"Clip-on","Surge current":"250 A","Earthing system":"TT TN IT","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"3","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IEC 61009-1","Device short name":"iC60H2 RCBO","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom","[In] rated current":"10 A at 50 °C","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection","Connections - terminals":"Screw clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Earth-leakage protection":"Integrated","Provision for padlocking":"Padlockable with padlock Ø 4 mm","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Circuit breaker application":"Distribution","Locking options description":"ON/OFF locking facilities","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230/240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage dependent","Ambient air temperature for operation":"-15...60 °C","[Ics] rated service breaking capacity":"7500 A at 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","[Icw] rated short-time withstand current":"Icw: 250 A during 8/20 µs impulse withstand","Comb busbar and distribution block compatibility":"NO"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9D51210/acti9-ic60h-rcbo-2p-10-a-c-curve-10-ka-300-ma-a-type/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D51210/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9D51210?","answer":"The A9D51210 is sourced and quoted to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is A9D51210's listed depth?","answer":"The A9D51210 has a depth of 77.5 mm, fitting standard distribution board depths."},{"question":"What compliance documentation does this RCBO carry?","answer":"The A9D51210 is certified to IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1, and is suitable for isolation. It carries tropicalisation class 2 for high-humidity environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D51210","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D51210 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}