{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D52606","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D52606","canonicalUrl":"https://aoctrl.com/schneider/A9D52606","factsUrl":"https://aoctrl.com/api/mcp/products/A9D52606","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 6 A, C-curve, 100 mA earth leakage, 6 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric A9D52606 is an Acti9 iDPN Vigi RCBO — a combined overcurrent and earth-leakage protection device in a single 36 mm wide module, 1P+N poles, rated 6 A with a C-curve magnetic trip (5...10 x In) and 100 mA residual current sensitivity. The 6 A rated current (In) and C-curve mean the thermal-magnetic trip holds steady up to 6 A continuous load and trips magnetically between 30 A and 60 A for short-circuit or high-inrush events — typical for lighting or general-purpose socket circuits where inrush isn't extreme. The 100 mA earth-leakage sensitivity is less sensitive than a 30 mA unit; it's suited for circuits where nuisance tripping from leakage in long cable runs or equipment with natural leakage (like heaters or older motors) would be a problem, while still providing personnel protection in some industrial settings. Neutral on the left, phase on the right — standard for the iDPN Vigi range.","metaTitle":"Schneider Electric A9D52606 Acti9 iDPN Vigi RCBO, 6 A C-curv","metaDescription":"Schneider Electric A9D52606 Acti9 iDPN Vigi RCBO. 6 A rated, C-curve, 100 mA earth leakage, 6 kA breaking capacity. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/A9D52606/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-idpn-n-vigi-1p+n-6a-c-curve-6000a-a-type-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D52606/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9D52606?","answer":"The A9D52606 has a breaking capacity of 6000 A Icn at 230...240 V AC 50 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What is the earth-leakage sensitivity of A9D52606?","answer":"The earth-leakage sensitivity is 100 mA, integrated into the device."},{"question":"Where can I buy the A9D52606?","answer":"The A9D52606 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D52606","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D52606 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}