{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D52625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D52625","canonicalUrl":"https://aoctrl.com/schneider/A9D52625","factsUrl":"https://aoctrl.com/api/mcp/products/A9D52625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 25 A, C-curve, 100 mA earth-leakage sensitivity, 6000 A Icn, clip-on DIN rail, white.","salesMarkdown":"Rated 25 A with a C-curve magnetic trip (5...10 x In) and 100 mA residual-current sensitivity, it breaks up to 6000 A Icn at 230...240 V AC, 50 Hz, per EN/IEC 61009-2-1. The thermal-magnetic trip unit handles both overload and short-circuit; the integrated earth-leakage element covers ground faults. This is the outgoer protection for final subcircuits in distribution boards. The 25 A rated current and C-curve mean this RCBO is sized for general-purpose socket-outlet circuits and small inductive loads — lighting, small motors, control transformers — where inrush can reach 5–10 times the rated current without nuisance tripping. The 100 mA earth-leakage threshold is higher than the 30 mA used for personal shock protection; it suits circuits where some standing leakage is normal (long cable runs, industrial equipment with filters) and the goal is fire protection or equipment damage prevention rather than personnel safety. Terminals accept 1...16 mm² rigid or 1...10 mm² flexible (with or without ferrule); strip length 15 mm, tighten to 2 N.m. IP20 on the front, IP40 inside the modular enclosure. The toggle gives local ON/OFF/fault-trip indication.","metaTitle":"Schneider Electric A9D52625 Acti9 iDPN Vigi RCBO, 25 A, C-cu","metaDescription":"Schneider Electric A9D52625 Acti9 iDPN Vigi RCBO, 25 A rated, C-curve, 100 mA earth leakage, 6000 A breaking capacity, current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/uk/en/product/A9D52625/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-idpn-n-vigi-1p+n-25a-c-curve-6000a-a-type-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D52625/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9D52625?","answer":"6000 A Icn at 230...240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What earth-leakage sensitivity does this RCBO have?","answer":"100 mA, integrated into the device."},{"question":"Where can I buy A9D52625 and how is it quoted?","answer":"Sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D52625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D52625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}