{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D53616","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D53616","canonicalUrl":"https://aoctrl.com/schneider/A9D53616","factsUrl":"https://aoctrl.com/api/mcp/products/A9D53616","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 16 A, C-curve, 30 mA earth leakage, 6 kA Icn, clip-on DIN rail, white.","salesMarkdown":"## What this RCBO does in the panel The 6 kA Icn breaking capacity at 230...240 V AC, 50 Hz, conforms to EN/IEC 61009-2-1, covering the majority of residential and light-commercial distribution boards. Clip-on mounting on DIN rail, 36 mm wide, with the neutral on the left and a 9 mm phase-to-neutral pitch — standard for Acti9 enclosures. Mounts on DIN rail via clip-on — no screws. Tightening torque 2 N.m top or bottom; strip length 15 mm. The 9 mm pitch between phase and neutral matches the Acti9 busbar system. IP20 on the device body, IP40 inside the modular enclosure.","metaTitle":"Schneider Electric A9D53616 Acti9 iDPN Vigi RCBO, 16 A, 30 m","metaDescription":"Schneider Electric A9D53616 Acti9 iDPN Vigi RCBO, 16 A rated, C-curve, 6 kA breaking capacity, 30 mA earth leakage, current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9D53616/acti-9-idpn-n-vigi-rcbo-1p+n-16a-c-curve-6000a-100ma-type-asi/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D53616/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9D53616?","answer":"Submit an RFQ through this listing. We source the A9D53616 through independent distribution and confirm current pricing and availability at quote time."},{"question":"What is A9D53616's listed depth (73 mm) on this component line?","answer":"The A9D53616 has a depth of 73 mm, a width of 36 mm, and a height of 85 mm — dimensions that fit standard Acti9 distribution board cutouts."},{"question":"What is A9D53616's listed range (Acti9) on this component line?","answer":"The A9D53616 belongs to the Schneider Electric Acti9 range, specifically the iDPN Vigi series of combined RCBOs."},{"question":"What compliance documentation does this brand provide for A9D53616 (RoHS, REACH, UL, IEC)?","answer":"The A9D53616 is designed and tested to EN/IEC 61009-2-1. It carries tropicalisation class 2 per IEC 60068-1. For RoHS, REACH, and UL declarations, contact your Schneider Electric representative or request documentation with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D53616","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D53616 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}