{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D53625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D53625","canonicalUrl":"https://aoctrl.com/schneider/A9D53625","factsUrl":"https://aoctrl.com/api/mcp/products/A9D53625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 25 A, C-curve, 6 kA Icn at 230 V AC, 100 mA earth leakage, thermal-magnetic, DIN rail, IP20.","salesMarkdown":"It combines a 25 A thermal-magnetic trip unit (curve C) with integrated 100 mA earth-leakage protection in a single 36 mm wide module that clips onto a DIN rail. The 25 A rated current and C-curve magnetic release (5…10 × In) mean this RCBO handles general-purpose loads like lighting, socket circuits, and small appliances where inrush from motors or capacitors is moderate. The 100 mA earth-leakage threshold is set above the 30 mA required for personal shock protection — it is sized for equipment protection or circuits where nuisance tripping from leakage in fixed appliances would be a problem. The 6 kA Icn is the short-circuit breaking capacity at service voltage; coordination with an upstream MCB or fuse is needed if the prospective fault current exceeds that level. IP20 body means it belongs inside an enclosure — not in a wet or washdown location. The toggle provides local ON/OFF/trip indication.","metaTitle":"Schneider Electric A9D53625 Acti9 iDPN Vigi 25A C-Curve RCBO","metaDescription":"Schneider Electric A9D53625 Acti9 iDPN Vigi RCBO, 25A rated, C-curve, 6kA breaking capacity, 100mA earth leakage, thermal-magnetic trip. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/90592b330996e0de3af2056ffb25f1a8.pdf","sourceUrl":"https://www.se.com/ng/en/product/A9D53625/residual-current-breaker-with-overcur-prot-rcbo-acti9-idpn-n-vigi-1p+n-25a-c-curve-6000a-asi-type-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D53625/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9D53625 and get current pricing?","answer":"The A9D53625 is sourced to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ."},{"question":"What is the breaking capacity of the A9D53625?","answer":"The breaking capacity is 6000 A Icn at 230…240 V AC 50 Hz conforming to EN/IEC 61009-2-1. This covers the fault level in most residential and light commercial distribution boards."},{"question":"What earth-leakage sensitivity does the A9D53625 have?","answer":"The integrated earth-leakage protection is set at 100 mA sensitivity. This is sized for equipment protection or circuits with fixed appliances where nuisance tripping on a 30 mA device would be an issue."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D53625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D53625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}