{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9D53640","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9D53640","canonicalUrl":"https://aoctrl.com/schneider/A9D53640","factsUrl":"https://aoctrl.com/api/mcp/products/A9D53640","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 40 A, C-curve, 6 kA breaking capacity, 100 mA earth leakage, DIN rail clip-on, white.","salesMarkdown":"It protects a single outgoing final circuit against overload, short-circuit (thermal-magnetic trip, C-curve 5...10 x In), and earth leakage at 100 mA sensitivity. Rated 40 A with 6 kA breaking capacity at 230...240 V AC, 50 Hz, it clips onto a DIN rail and is intended for distribution boards in residential or light commercial installations. The 40 A rated current and C-curve (5–10 x In magnetic trip) means this RCBO is sized for general-purpose resistive and moderate inductive loads — lighting, socket outlets, small appliances — not for motor starting or high-inrush circuits where a D-curve would be needed. Integrated 100 mA earth-leakage protection (sensitivity) provides fire protection and indirect-contact protection, not personal shock protection (that requires 30 mA or lower). Typical placement is as an outgoer in the distribution board, protecting a circuit where the loop impedance or equipment leakage makes a separate RCD + MCB combination desirable. Clip-on mounting to DIN rail (EN 60715). The module occupies 4 pitches at 9 mm per pole — 36 mm total width. Neutral is on the left. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible (with or without ferrule); strip length 15 mm, tightening torque 2 N.m. IP20 rated (IP40 in modular enclosure). Limitation class 3 per that standard.","metaTitle":"A9D53640 Acti9 iDPN Vigi MCB, 40A C-curve, 6kA, 100mA RCD","metaDescription":"Schneider Electric Acti9 iDPN Vigi A9D53640, 40A C-curve MCB with integrated 100mA RCD, 6kA breaking capacity, DIN rail mount, current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN Vigi","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Device short name":"iDPN N Vigi","Network frequency":"50 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"40 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Single terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9D53640/acti-9-idpn-n-vigi-rcbo-1p+n-40a-c-curve-6000a-100ma-type-asi/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9D53640/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9D53640 and get a price?","answer":"The A9D53640 is sourced and quoted to order through independent distribution; submit an RFQ for current availability and pricing."},{"question":"What is the breaking capacity of the A9D53640?","answer":"The breaking capacity is 6000 A Icn at 230...240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1."},{"question":"What does the C-curve on this RCBO mean?","answer":"The C-curve means the magnetic trip operates at 5 to 10 times the rated current (200–400 A for this 40 A unit), suitable for general-purpose loads with moderate inrush."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9D53640","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9D53640 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}